XLP 600VOLT BUILDING WIRE
TYPE XHHW-2
SINGLE COPPER CONDUCTOR, 90°C WET/DRY

Construction:
CONDUCTOR: SOLID OR STRANDED ANNEALED BARE COPPER.
INSULATION: CROSS-LINKED POLYETHYLENE (XLP).
 Charlotte Wire Part# ↓   Size AWG   Number of Strands   XLP Ins. Thickness (in.)   Ampacity 90°C*   Approx. O.D. (in.)   Net Wt. (Lbs/Mft)   Add to Quote Cart 
CW01151 14 1 0.03 25** .13" 18 Request Quote For This Product 
CW01152 12 1 0.03 30** .14" 26 Request Quote For This Product 
CW01153 10 1 0.03 40** .16" 38 Request Quote For This Product 
CW01154 14 7 0.03 25** .14" 18 Request Quote For This Product 
CW01155 12 7 0.03 30** .16" 27 Request Quote For This Product 
CW01156 10 7 0.03 40** .18" 40 Request Quote For This Product 
CW01157 8 7 0.045 55 .24" 66 Request Quote For This Product 
CW01158 6 7 0.045 75 .28" 99 Request Quote For This Product 
CW01159 4 7 0.045 95 .33" 151 Request Quote For This Product 
CW01160 3 7 0.045 110 .35" 190 Request Quote For This Product 
CW01161 2 7 0.045 130 .39" 231 Request Quote For This Product 
CW01162 1 19 0.055 150 .45" 298 Request Quote For This Product 
CW01163 1/0 19 0.055 170 .49" 368 Request Quote For This Product 
CW01164 2/0 19 0.055 195 .54" 456 Request Quote For This Product 
CW01165 3/0 19 0.055 225 .59" 570 Request Quote For This Product 
CW01166 4/0 19 0.055 260 .65" 710 Request Quote For This Product 
CW01167 250MCM 37 0.065 290 .72" 840 Request Quote For This Product 
CW01168 300MCM 37 0.065 320 .77" 1000 Request Quote For This Product 
CW01169 350MCM 37 0.065 350 .82" 1160 Request Quote For This Product 
CW01170 400MCM 37 0.065 380 .87" 1320 Request Quote For This Product 
CW01171 500MCM 37 0.065 430 .95" 1640 Request Quote For This Product 
CW01172 600MCM 61 0.08 475 1.05" 1985 Request Quote For This Product 
CW01173 750MCM 61 0.08 535 1.16" 2460 Request Quote For This Product 
CW01174 1000MCM 61 0.08 615 1.32" 3260 Request Quote For This Product 
Displaying 1 to 24 (of 24 products) Result Pages:  1 
* Ampacity in accordance with NEC for not more than 3 conductors at 90°C conductor temperature and 30°C ambient temperature in wet or dry locations per Table 310-16.
** Overcurrent protection shall not exceed 15amps for 14AWG, 20amps for 12AWG, and 30amps for 10AWG.
Application
General purpose building wire up to 600Volts with conductor temperatures of 90°C maximum in wet or dry locations.
XLP features good chemical resistance and is also suitable for low leakage circuits requiring dielectric constant of 3.5 or less.
Standards
UL 44: Type XHHW-2.
ICEA S-95-658/NEMA WC70 for Nonshielded 0 - 2KV Cables (Formerly ICEA S-66-524/NEMA WC7).
Options
VW1 rated insulation.
CT Use: sizes 1/0 and larger.
Tinned copper conductors.