XLP 600VOLT BUILDING WIRE
TYPE RHH/RHW-2/USE-2
SINGLE COPPER CONDUCTOR, 90°C WET/DRY

Construction:
CONDUCTOR: SOLID OR STRANDED ANNEALED BARE COPPER.
INSULATION: CROSS-LINKED POLYETHYLENE (XLP).
 Charlotte Wire Part# ↓   Size AWG   Number of Strands   XLP Ins. Thickness (in.)   Ampacity 90°C*   Approx. O.D. (in.)   Approx. Net Wt. (Lbs/Mft)   Add to Quote Cart 
CW01176 14 1 0.045" 25** 0.16" 20 Request Quote For This Product 
CW01177 12 1 0.045" 30** 0.17" 30 Request Quote For This Product 
CW01178 10 1 0.045" 40** 0.19" 44 Request Quote For This Product 
CW01179 14 7 0.045" 25** 0.17" 21 Request Quote For This Product 
CW01180 12 7 0.045" 30** 0.19" 31 Request Quote For This Product 
CW01181 10 7 0.045" 40** 0.21" 46 Request Quote For This Product 
CW01182 8 7 0.045" 55 0.27" 72 Request Quote For This Product 
CW01183 6 7 0.060" 75 0.31" 106 Request Quote For This Product 
CW01184 4 7 0.060" 95 0.36" 160 Request Quote For This Product 
CW01185 3 7 0.060" 110 0.38" 200 Request Quote For This Product 
CW01186 2 7 0.060" 130 0.42" 243 Request Quote For This Product 
CW01187 1 19 0.080" 150 0.50" 312 Request Quote For This Product 
CW01188 1/0 19 0.080" 170 0.55" 385 Request Quote For This Product 
CW01189 2/0 19 0.080" 195 0.59" 478 Request Quote For This Product 
CW01190 3/0 19 0.080" 225 0.63" 592 Request Quote For This Product 
CW01191 4/0 19 0.080" 260 0.69" 735 Request Quote For This Product 
CW01192 250MCM 37 0.095" 290 0.78" 875 Request Quote For This Product 
CW01193 300MCM 37 0.095" 320 0.83" 1030 Request Quote For This Product 
CW01194 350MCM 37 0.095" 350 0.87" 1202 Request Quote For This Product 
CW01195 400MCM 37 0.095" 380 0.92" 1350 Request Quote For This Product 
CW01196 500MCM 37 0.095" 430 1.00" 1688 Request Quote For This Product 
CW01197 600MCM 61 0.110" 475 1.10" 2015 Request Quote For This Product 
CW01198 750MCM 61 0.110" 535 1.22" 2510 Request Quote For This Product 
CW01199 1000MCM 61 0.110" 615 1.39" 3300 Request Quote For This Product 
Displaying 1 to 24 (of 24 products) Result Pages:  1 
* Ampacity in accordance with NEC for not more than 3 conductors at 90°C conductor temperature and 30°C ambient temperature in wet or dry locations per Table 310-16.
** Overcurrent protection shall not exceed 15amps for 14AWG, 20amps for 12AWG, and 30amps for 10AWG.
Application
General purpose building wire up to 600Volts with conductor temperatures of 90°C maximum in wet or dry locations.
May be directly buried.
XLP features moisture and chemical resistance.
Also suitable for airport applications per FAA-L-824 Type C (sizes 14 AWG through 4/0)
Standards
UL 44: Type RHH 90C Dry. Type RHW-2 90C Wet.
UL 854: Type USE-2 90°C Direct Burial
ICEA S-95-658/NEMA WC70 for Nonshielded 0 - 2KV Cables (formerly ICEA S-66-524/NEMA WC7).
Optional Constructions
VW1 rated insulation.
CT Use: sizes 1/0 and larger.
Tinned copper conductors.