XLP 600VOLT BUILDING WIRE
TYPE RHH/RHW-2/USE-2
SINGLE COPPER CONDUCTOR, 90°C WET/DRY
| Construction: |
| CONDUCTOR: |
SOLID OR STRANDED ANNEALED BARE COPPER.
|
| INSULATION: |
CROSS-LINKED POLYETHYLENE (XLP).
|
| Charlotte Wire Part# ↓ |
Size AWG |
Number of Strands |
XLP Ins. Thickness (in.) |
Ampacity 90°C* |
Approx. O.D. (in.) |
Approx. Net Wt. (Lbs/Mft) |
Add to Quote Cart |
| CW01176 |
14 |
1 |
0.045" |
25** |
0.16" |
20 |
|
| CW01177 |
12 |
1 |
0.045" |
30** |
0.17" |
30 |
|
| CW01178 |
10 |
1 |
0.045" |
40** |
0.19" |
44 |
|
| CW01179 |
14 |
7 |
0.045" |
25** |
0.17" |
21 |
|
| CW01180 |
12 |
7 |
0.045" |
30** |
0.19" |
31 |
|
| CW01181 |
10 |
7 |
0.045" |
40** |
0.21" |
46 |
|
| CW01182 |
8 |
7 |
0.045" |
55 |
0.27" |
72 |
|
| CW01183 |
6 |
7 |
0.060" |
75 |
0.31" |
106 |
|
| CW01184 |
4 |
7 |
0.060" |
95 |
0.36" |
160 |
|
| CW01185 |
3 |
7 |
0.060" |
110 |
0.38" |
200 |
|
| CW01186 |
2 |
7 |
0.060" |
130 |
0.42" |
243 |
|
| CW01187 |
1 |
19 |
0.080" |
150 |
0.50" |
312 |
|
| CW01188 |
1/0 |
19 |
0.080" |
170 |
0.55" |
385 |
|
| CW01189 |
2/0 |
19 |
0.080" |
195 |
0.59" |
478 |
|
| CW01190 |
3/0 |
19 |
0.080" |
225 |
0.63" |
592 |
|
| CW01191 |
4/0 |
19 |
0.080" |
260 |
0.69" |
735 |
|
| CW01192 |
250MCM |
37 |
0.095" |
290 |
0.78" |
875 |
|
| CW01193 |
300MCM |
37 |
0.095" |
320 |
0.83" |
1030 |
|
| CW01194 |
350MCM |
37 |
0.095" |
350 |
0.87" |
1202 |
|
| CW01195 |
400MCM |
37 |
0.095" |
380 |
0.92" |
1350 |
|
| CW01196 |
500MCM |
37 |
0.095" |
430 |
1.00" |
1688 |
|
| CW01197 |
600MCM |
61 |
0.110" |
475 |
1.10" |
2015 |
|
| CW01198 |
750MCM |
61 |
0.110" |
535 |
1.22" |
2510 |
|
| CW01199 |
1000MCM |
61 |
0.110" |
615 |
1.39" |
3300 |
|
| Displaying 1 to 24 (of 24 products) |
Result Pages: 1 |
| * Ampacity in accordance with NEC for not more than 3 conductors at 90°C conductor temperature and 30°C ambient temperature in wet or dry locations per Table 310-16.
|
| ** Overcurrent protection shall not exceed 15amps for 14AWG, 20amps for 12AWG, and 30amps for 10AWG.
|
| Application |
| General purpose building wire up to 600Volts with conductor temperatures of 90°C maximum in wet or dry locations.
|
| May be directly buried.
|
| XLP features moisture and chemical resistance.
|
| Also suitable for airport applications per FAA-L-824 Type C (sizes 14 AWG through 4/0)
|
| Standards |
| UL 44: Type RHH 90C Dry. Type RHW-2 90C Wet.
|
| UL 854: Type USE-2 90°C Direct Burial
|
| ICEA S-95-658/NEMA WC70 for Nonshielded 0 - 2KV Cables (formerly ICEA S-66-524/NEMA WC7).
|
| Optional Constructions |
| VW1 rated insulation.
|
| CT Use: sizes 1/0 and larger.
|
| Tinned copper conductors.
|
|
|