600VOLT ALUMINUM BUILDING WIRE
TYPE USE-2 / RHH / RHW-2
SINGLE ALUMINUM CONDUCTOR 90°C WET/DRY

Construction:
CONDUCTOR: COMPACT STRANDED 8000 SERIES ALUMINUM ALLOY.
INSULATION: CROSS-LINKED POLYETHYLENE (XLP).
 Charlotte Wire Part# ↑   Size AWG   Number of Strands   XLP Ins. Thickness (in.)   Ampacity 90°C*   Approx. O.D. (in.)   Approx. Net Wt. (Lbs/Mft)   Add to Quote Cart 
CW01443 1000MCM 61 0.11 500 1.29" 1150 Request Quote For This Product 
CW01442 750MCM 61 0.11 435 1.14" 885 Request Quote For This Product 
CW01441 700MCM 61 0.11 420 1.11" 830 Request Quote For This Product 
CW01440 600MCM 61 0.11 385 1.04" 720 Request Quote For This Product 
CW01439 500MCM 37 0.095 350 .94" 598 Request Quote For This Product 
CW01438 400MCM 37 0.095 305 .86" 490 Request Quote For This Product 
CW01437 350MCM 37 0.095 280 .82" 440 Request Quote For This Product 
CW01436 300MCM 37 0.095 255 .77" 385 Request Quote For This Product 
CW01435 250MCM 37 0.095 230 .72" 325 Request Quote For This Product 
CW01434 4/0 19 0.08 205 .64" 270 Request Quote For This Product 
CW01433 3/0 19 0.08 175 .60" 222 Request Quote For This Product 
CW01432 2/0 19 0.08 150 .55" 184 Request Quote For This Product 
CW01431 1/0 19 0.08 135 .51" 152 Request Quote For This Product 
CW01430 1 19 0.08 115 .47" 127 Request Quote For This Product 
CW01429 2 7 0.06 100 .39" 95 Request Quote For This Product 
CW01428 4 7 0.06 75 .34" 66 Request Quote For This Product 
CW01427 6 7 0.06 60 .29" 50 Request Quote For This Product 
CW01426 8 7 0.06 45 .27" 38 Request Quote For This Product 
Displaying 1 to 18 (of 18 products) Result Pages:  1 
* Ampacity in accordance with NEC for not more than 3 conductors at 90°C conductor temperature and 30°C ambient temperature in wet or dry locations per Table 310-16.
Application
General purpose building wire up to 600Volts with conductor temperatures of 90°C maximum in wet or dry locations, including direct burial.
Standards
UL 44: Type RHH & RHW-2.
UL 854: Type USE-2.
Federal Spec.: JC-30B.
ASTM Standards B-800 and B-801.