ALUMINUM TRIPLEX OVERHEAD
2/C INSULATED PLUS ACSR MESSENGER
Construction:
CONDUCTOR:
SOLID OR STRANDED COMPRESSED 1350-H19 ALUMINUM.
INSULATION:
POLYETHYLENE OR CROSSLINKED POLYETHYLENE (XLP).
ASSEMBLY:
2 INSULATED CONDUCTORS TWISTED AROUND AN ALUMINUM CONDUCTOR STEEL REINFORCED (ACSR) STRANDED NEUTRAL/MESSENGER.
Charlotte Wire Part# ↓
Code Word
Size AWG
Strands
Insulation Thickness (in.)
Messenger Size AWG
Breaking Strength (Lbs)
Approx. Net Wt. (Lbs/Mft)
Add to Quote Cart
CW01451
Paludina
6
1
0.045
6
1190
115
CW01452
Voluta
6
7
0.045
6
1190
120
CW01453
Whelk
4
1
0.045
4
1860
167
CW01454
Periwinkle
4
7
0.045
4
1860
176
CW01455
Conch
2
7
0.045
2
2850
270
CW01456
Neritina
1/0
7
0.06
1/0
4380
430
CW01457
Cenia
1/0
19
0.06
1/0
4380
425
CW01458
Runcina
2/0
7
0.06
2/0
5310
530
CW01459
Triton
2/0
19
0.06
2/0
5310
522
CW01460
Mursia
3/0
19
0.06
3/0
6620
645
CW01461
Zuzara
4/0
19
0.06
4/0
8350
800
CW01462
Limpet
336.4MCM
19
0.08
336.4MCM
8680
1190
Displaying
1
to
12
(of
12
products)
Result Pages:
1
Application
To be used as an overhead power supply for service at 600Volts or less.
Standards
ASTM B-230: Aluminum Wire (1350-H19).
ASTM B-231: Aluminum Conductors - Concentric Lay Stranded.
ASTM B-232: Aluminum Conductor Steel Reinforced (ACSR).
ICEA S-76-474: For Service Drop Cable.