XLP/HYPALON® TRAY CABLE - #16AWG
TYPE TC - SUNLIGHT RESISTANT,DIRECT BURIAL
XLP INSULATION, CSPE JACKET, 600VOLTS

Construction:
CONDUCTOR: 7 STRANDED TINNED ANNEALED COPPER.
INSULATION: FLAME-RETARDANT CROSSLINKED POLYETHYLENE (XLP) TYPE XHHW-2 VW1 PER UL 44. INSULATED CONDUCTORS RATED 90°C WET OR DRY.
CONDUCTOR IDENTIFICATION: INSULATED CONDUCTORS ARE COLOR CODED PER ICEA METHOD 1 TABLE E-2 OF ICEA S-73-532. (FORMERLY K-2).*
ASSEMBLY: CONDUCTORS ARE CABLED TOGETHER WITH A SUITABLE TAPE SEPARATOR AS NEEDED.
OVERALL JACKET: SUNLIGHT RESISTANT, FLAME RETARDANT BLACK HYPALON® (CHLOROSULFONATED POLYETHYLENE) PER UL 1277, WHICH PROTECTS AGAINST HEAT, FLAME, CHEMICALS, MOISTURE, AND MECHANICAL DAMAGE.
 Charlotte Wire Part# ↓   Size AWG   Number of Conductors   Insulation Thickness (in.)   Jacket Thickness (in.)   Overall Diameter (in.)   Approx. Net Wt. (Lbs/Mft)   Add to Quote Cart 
CW02690 16 2 .030" .045" .35" 63 Request Quote For This Product 
CW02691 16 3 .030" .045" .37" 75 Request Quote For This Product 
CW02692 16 4 .030" .045" .40" 93 Request Quote For This Product 
CW02693 16 5 .030" .045" .43" 112 Request Quote For This Product 
CW02694 16 7 .030" .045" .47" 144 Request Quote For This Product 
CW02695 16 9 .030" .060" .57" 200 Request Quote For This Product 
Displaying 1 to 6 (of 6 products) Result Pages:  1 
® Hypalon® is a Dupont Trademark. (Also known as chlorosulfonated polyethylene or CSPE.)
*To specify Method 1 Table E-1(formerly K-1), add suffix "M1" to Charlotte Wire Part Number.
Application
Suitable for control, signal, or lighting circuits rated 600Volts in power plants and heavy industrial locations where flame-resistance, stability in heat, physical durability, and excellent reliability is needed.
May be used as sunlight resistant, directly buried, and wet or dry locations.
Per NEC Articles 336 and 392, approved for installation in
1) raceways and cable tray systems including ladders, troughs, channels, solid bottom trays, and other similar structures,
2) lighting, control, and signal circuits,
3) aerial locations where supported by a messenger wire,
4) hazardous locations per NEC Article 501 Class 1 Division 2, and
5) Class 1 circuits as permitted in NEC Article 725-21(B).
Standards
UL 1277 for Type TC Cables.
Passes UL and IEEE383 70,000 BTU and ICEA 210,000BTU flame test.
NEC Articles 336 & 392 for Tray cable uses and constructions.
ICEA S-95-658/NEMA WC70 for Nonshielded 0-2kv Cables. (Formerly ICEA S-66-524/NEMA WC-7).