LOW SMOKE TRAY CABLE - #14AWG
TYPE TC - SUNLIGHT RESISTANT, DIRECT BURIAL
XHHW-2 CONDUCTORS, LS XLPO JACKET 600VOLTS

Construction:
CONDUCTOR: 7 STRANDED BARE COPPER PER ASTM B-3.
INSULATION: THERMOSETTING CROSSLINKED POLYETHYLENE (XLP) TYPE XHHW-2 PER UL 44. INSULATED CONDUCTORS RATED 90°C WET OR DRY.
CONDUCTOR IDENTIFICATION: INSULATED CONDUCTORS ARE COLOR CODED PER ICEA METHOD 1 TABLE E-2 OF ICEA S-73-532 (FORMERLY K-2).*
ASSEMBLY: CONDUCTORS ARE CABLED TOGETHER WITH A SUITABLE TAPE SEPARATOR AS NEEDED.
OVERALL JACKET: SUNLIGHT RESISTANT, FLAME RETARDANT BLACK LOW SMOKE ZERO HALOGEN CROSSLINKED POLYOLEFIN (XLPO).
 Charlotte Wire Part# ↓   Size AWG   Number of Conductors   Insulation Thickness (in.)   Jacket Thickness (in.)   Overall Diameter (in.)   Approx. Net Wt. (Lbs/Mft.)   Add to Quote Cart 
CW02901 14 2 .030" .045" .25" x .38"** 65 Request Quote For This Product 
CW02902 14 3 .030" .045" 0.40" 92 Request Quote For This Product 
CW02903 14 4 .030" .045" 0.44" 118 Request Quote For This Product 
CW02904 14 5 .030" .045" 0.48" 140 Request Quote For This Product 
CW02905 14 7 .030" .045" 0.52" 180 Request Quote For This Product 
CW02906 14 9 .030" .060" 0.63" 250 Request Quote For This Product 
CW02907 14 10 .030" .060" 0.69" 275 Request Quote For This Product 
CW02908 14 12 .030" .060" 0.72" 310 Request Quote For This Product 
CW02909 14 15 .030" .060" 0.77" 380 Request Quote For This Product 
CW02910 14 19 .030" .060" 0.82" 460 Request Quote For This Product 
CW02911 14 20 .030" .080" 0.90" 520 Request Quote For This Product 
CW02912 14 25 .030" .080" 1.00" 640 Request Quote For This Product 
CW02913 14 30 .030" .080" 1.08" 740 Request Quote For This Product 
CW02914 14 37 .030" .080" 1.14" 890 Request Quote For This Product 
Displaying 1 to 14 (of 14 products) Result Pages:  1 
*To Specify Method 1 Table E-1(formerly K-1) add suffix "M1" to Charlotte Wire Part Number.
**Flat Construction
Application
Suitable for control, signal, or lighting circuits rated 600Volts in power plants and heavy industrial locations where flame-resistance, stability in heat, physical durability, and excellent reliability is needed. May be used as sunlight resistant, directly buried, and wet or dry locations. Per NEC Articles 336 and 392, approved for installation in 1)raceways and cable tray systems including ladders, troughs, channels, solid bottom trays, and other similar structures, 2)lighting, control, and signal circuits, 3)aerial locations where supported by a messenger wire, 4)hazardous locations per NEC Article 501 Class 1 Division 2, and 5)Class 1 circuits as permitted in NEC Article 725-21(B).
Standards
UL Standard 1277 for Type TC Cables.
Passes UL and IEEE383 70,000BTU and ICEA 210,000BTU flame test.
UL Standard 44 for XHHW-2 Conductors.
ICEA S-95-658/NEMA WC70 for Nonshielded 0-2KV Cables.
(Formerly ICEA S-66-524/NEMA WC70).
NEC Articles 336 &392 for Tray Cable Uses and Constructions.