LOW SMOKE TRAY CABLE 3 CONDUCTOR WITH GROUND
TYPE TC - SUNLIGHT RESISTANT, DIRECT BURIAL
XHHW-2 CONDUCTORS, LS XLPO JACKET 600VOLTS
Click  for Printer Friendly Spec Sheet. | Construction: |
| CONDUCTOR: |
CLASS B STRANDED COPPER.
|
| INSULATION: |
THERMOSETTING FLAME-RETARDANT CROSSLINKED POLYETHYLENE (XLP) TYPE XHHW-2 PER UL 44. INSULATED CONDUCTORS RATED 90°C WET OR DRY.
|
| CONDUCTOR IDENTIFICATION: |
INSULATED CONDUCTORS COLOR CODED PER ICEA METHOD 4(BLACK WITH PRINTED NUMBERS) ON #8 AND LARGER. SIZES #12 AND #10 COLOR PER ICEA METHOD 1 TABLE E-2(BLACK-RED-BLUE).
|
| ASSEMBLY: |
CONDUCTORS CABLED TOGETHER WITH A STRANDED COPPER GROUND WIRE IN ONE OF THE INTERSTICES, SUITABLE FILLERS FOR ROUNDNESS WHERE NEEDED, AND CABLE TAPE.
|
| OVERALL JACKET: |
SUNLIGHT RESISTANT, FLAME RETARDANT BLACK LOW SMOKE ZERO HALOGEN CROSSLINKED POLYOLEFIN (XLPO). |
| Charlotte Wire Part# ↑ |
Size AWG |
Number of Strands |
Insulation Thickness (in.) |
Jacket Thickness (in.) |
Ground Wire AWG |
Overall Diameter (in.) |
Approx. Net Wt. (Lbs/Mft) |
Add to Quote Cart |
| CW02977 |
1000MCM |
61 |
.080" |
.140" |
1/0 |
3.20" |
11700 |
|
| CW02976 |
750MCM |
61 |
.080" |
.110" |
1 |
2.84" |
8990 |
|
| CW02975 |
500MCM |
37 |
.065" |
.110" |
2 |
2.28" |
6080 |
|
| CW02974 |
350MCM |
37 |
.065" |
.110" |
3 |
2.00" |
4320 |
|
| CW02973 |
250MCM |
37 |
.065" |
.110" |
4 |
1.76" |
3230 |
|
| CW02972 |
4/0 |
19 |
.055" |
.080" |
4 |
1.57" |
2650 |
|
| CW02971 |
3/0 |
19 |
.055" |
.080" |
4 |
1.45" |
2260 |
|
| CW02970 |
2/0 |
19 |
.055" |
.080" |
6 |
1.33" |
1770 |
|
| CW02969 |
1/0 |
19 |
.055" |
.080" |
6 |
1.23" |
1490 |
|
| CW02968 |
1 |
19 |
.055" |
.080" |
6 |
1.16" |
1275 |
|
| CW02967 |
2 |
7 |
.045" |
.080" |
6 |
1.02" |
1015 |
|
| CW02966 |
4 |
7 |
.045" |
.080" |
8 |
0.88" |
686 |
|
| CW02965 |
6 |
7 |
.045" |
.060" |
8 |
0.76" |
460 |
|
| CW02964 |
8 |
7 |
.045" |
.060" |
10 |
0.68" |
332 |
|
| CW02963 |
10 |
7 |
.030" |
.045" |
10 |
0.565" |
208 |
|
| CW02962 |
12 |
7 |
.030" |
.045" |
12 |
0.48" |
149 |
|
| Displaying 1 to 16 (of 16 products) |
Result Pages: 1 |
| Application |
| Power circuits rated 600Volts in power plants and heavy industrial locations where flame-resistance, stability in heat, physical durability, and excellent reliability is needed. May be used as sunlight resistant, directly buried, and wet or dry locations. Per NEC Articles 336 and 392, approved for installation in 1)raceways and cable tray systems including ladders, troughs, channels, solid bottom trays, and other similar structures, 2)aerial locations where supported by a messenger wire and 3)hazardous locations per NEC Art.501 Class 1 Division 2.
|
| Standards |
| UL Standard 1277 for Type TC Cables.
|
| Passes UL and IEEE383 70,000BTU and ICEA 210,000BTU flame test.
|
| UL Standard 44 for Rubber Insulated Wire & Cable(XHHW-2).
|
| ICEA S-95-658/NEMA WC70 for Nonshielded 0-2KV Cables.
|
| (Formerly ICEA S-66-524/NEMA WC70).
|
| NEC Articles 336 &392 for Tray Cable Uses and Constructions. |
|