LOW SMOKE TRAY CABLE 3 CONDUCTOR WITH GROUND
TYPE TC - SUNLIGHT RESISTANT, DIRECT BURIAL
XHHW-2 CONDUCTORS, LS XLPO JACKET 600VOLTS

Construction:
CONDUCTOR: CLASS B STRANDED COPPER.
INSULATION: THERMOSETTING FLAME-RETARDANT CROSSLINKED POLYETHYLENE (XLP) TYPE XHHW-2 PER UL 44. INSULATED CONDUCTORS RATED 90°C WET OR DRY.
CONDUCTOR IDENTIFICATION: INSULATED CONDUCTORS COLOR CODED PER ICEA METHOD 4(BLACK WITH PRINTED NUMBERS) ON #8 AND LARGER. SIZES #12 AND #10 COLOR PER ICEA METHOD 1 TABLE E-2(BLACK-RED-BLUE).
ASSEMBLY: CONDUCTORS CABLED TOGETHER WITH A STRANDED COPPER GROUND WIRE IN ONE OF THE INTERSTICES, SUITABLE FILLERS FOR ROUNDNESS WHERE NEEDED, AND CABLE TAPE.
OVERALL JACKET: SUNLIGHT RESISTANT, FLAME RETARDANT BLACK LOW SMOKE ZERO HALOGEN CROSSLINKED POLYOLEFIN (XLPO).
 Charlotte Wire Part# ↓   Size AWG   Number of Strands   Insulation Thickness (in.)   Jacket Thickness (in.)   Ground Wire AWG   Overall Diameter (in.)   Approx. Net Wt. (Lbs/Mft)   Add to Quote Cart 
CW02962 12 7 .030" .045" 12 0.48" 149 Request Quote For This Product 
CW02963 10 7 .030" .045" 10 0.565" 208 Request Quote For This Product 
CW02964 8 7 .045" .060" 10 0.68" 332 Request Quote For This Product 
CW02965 6 7 .045" .060" 8 0.76" 460 Request Quote For This Product 
CW02966 4 7 .045" .080" 8 0.88" 686 Request Quote For This Product 
CW02967 2 7 .045" .080" 6 1.02" 1015 Request Quote For This Product 
CW02968 1 19 .055" .080" 6 1.16" 1275 Request Quote For This Product 
CW02969 1/0 19 .055" .080" 6 1.23" 1490 Request Quote For This Product 
CW02970 2/0 19 .055" .080" 6 1.33" 1770 Request Quote For This Product 
CW02971 3/0 19 .055" .080" 4 1.45" 2260 Request Quote For This Product 
CW02972 4/0 19 .055" .080" 4 1.57" 2650 Request Quote For This Product 
CW02973 250MCM 37 .065" .110" 4 1.76" 3230 Request Quote For This Product 
CW02974 350MCM 37 .065" .110" 3 2.00" 4320 Request Quote For This Product 
CW02975 500MCM 37 .065" .110" 2 2.28" 6080 Request Quote For This Product 
CW02976 750MCM 61 .080" .110" 1 2.84" 8990 Request Quote For This Product 
CW02977 1000MCM 61 .080" .140" 1/0 3.20" 11700 Request Quote For This Product 
Displaying 1 to 16 (of 16 products) Result Pages:  1 
Application
Power circuits rated 600Volts in power plants and heavy industrial locations where flame-resistance, stability in heat, physical durability, and excellent reliability is needed. May be used as sunlight resistant, directly buried, and wet or dry locations. Per NEC Articles 336 and 392, approved for installation in 1)raceways and cable tray systems including ladders, troughs, channels, solid bottom trays, and other similar structures, 2)aerial locations where supported by a messenger wire and 3)hazardous locations per NEC Art.501 Class 1 Division 2.
Standards
UL Standard 1277 for Type TC Cables.
Passes UL and IEEE383 70,000BTU and ICEA 210,000BTU flame test.
UL Standard 44 for Rubber Insulated Wire & Cable(XHHW-2).
ICEA S-95-658/NEMA WC70 for Nonshielded 0-2KV Cables.
(Formerly ICEA S-66-524/NEMA WC70).
NEC Articles 336 &392 for Tray Cable Uses and Constructions.