VNTC TRAY CABLE - #18AWG NONSHIELDED
TYPE TC - SUNLIGHT RESISTANT,DIRECT BURIAL
TFN CONDUCTORS, PVC JACKET, 600VOLTS,UL 1277
Click  for Printer Friendly Spec Sheet. | Construction: |
| CONDUCTOR: |
7 STRANDED BARE COPPER PER ASTM B-3.
|
| INSULATION: |
POLYVINYLCHLORIDE WITH NYLON JACKET TYPE TFN PER UL 62 (GASOLINE AND OIL RESISTANT)
|
| CONDUCTOR IDENTIFICATION: |
INSULATED CONDUCTORS ARE COLOR CODED PER ICEA METHOD 1 TABLE E-2 OF ICEA S-73-532 (FORMERLY K-2).*
|
| ASSEMBLY: |
CONDUCTORS ARE CABLED TOGETHER WITH A SUITABLE TAPE SEPARATOR AS NEEDED.
|
| OVERALL JACKET: |
SUNLIGHT RESISTANT, FLAME RETARDANT BLACK PVC PER UL 1277, WHICH PROTECTS AGAINST HEAT, FLAME, CHEMICALS, MOISTURE, AND MECHANICAL DAMAGE.
|
| Charlotte Wire Part# ↓ |
Size AWG |
Number of Conductors |
Insulation Thickness (in.) |
Nylon Thickness (in.) |
Jacket Thickness (in.) |
Overall Diameter (in.) |
Approx. Net Wt. (Lbs/Mft) |
Add to Quote Cart |
| CW02001 |
18 |
2 |
0.015 |
0.004 |
0.045 |
.18" x .27"** |
35 |
|
| CW02002 |
18 |
3 |
0.015 |
0.004 |
0.045 |
.29" |
45 |
|
| CW02003 |
18 |
4 |
0.015 |
0.004 |
0.045 |
.31" |
54 |
|
| CW02004 |
18 |
5 |
0.015 |
0.004 |
0.045 |
.34" |
65 |
|
| CW02005 |
18 |
6 |
0.015 |
0.004 |
0.045 |
.36" |
77 |
|
| CW02006 |
18 |
7 |
0.015 |
0.004 |
0.045 |
.36" |
82 |
|
| CW02007 |
18 |
8 |
0.015 |
0.004 |
0.045 |
.39" |
93 |
|
| CW02008 |
18 |
9 |
0.015 |
0.004 |
0.045 |
.42" |
103 |
|
| CW02009 |
18 |
10 |
0.015 |
0.004 |
0.045 |
.45" |
114 |
|
| CW02010 |
18 |
12 |
0.015 |
0.004 |
0.045 |
.46" |
130 |
|
| CW02011 |
18 |
15 |
0.015 |
0.004 |
0.045 |
.50" |
157 |
|
| CW02012 |
18 |
19 |
0.015 |
0.004 |
0.06 |
.58" |
208 |
|
| CW02013 |
18 |
25 |
0.015 |
0.004 |
0.06 |
.65" |
264 |
|
| CW02014 |
18 |
30 |
0.015 |
0.004 |
0.06 |
.70" |
309 |
|
| CW02015 |
18 |
37 |
0.015 |
0.004 |
0.06 |
.75" |
370 |
|
| Displaying 1 to 15 (of 15 products) |
Result Pages: 1 |
| *To specify Method 1 Table E-1(formerly K-1), add suffix "M1" to Charlotte Wire Part Number.
|
| ** Flat Construction
|
| Application |
| Control, Signal, or Lighting circuits rated 600Volts. May be used as sunlight resistant, directly buried and wet or dry locations.
|
| Per NEC Articles 336 and 392, approved for installation in
|
| 1) raceways and cable tray systems including ladders, troughs, channels, solid bottom trays, and other similar structures,
|
| 2) lighting, control, and signal circuits
|
| 3) aerial locations where supported by a messenger wire
|
| 4) hazardous locations per Art.501 Class 1 Division 2,
|
| 5) Class 1 circuits as permitted in Article 725-21(B).
|
| Standards |
| UL Standard 1277 for Type TC Cables.
|
| Passes UL and IEEE383 70,000BTU Flame Test
|
| UL Standard 62 for TFN Conductors.
|
| NEC Articles 336 and 392 for Tray Cable uses and constructions
|
|