VNTC TRAY CABLE - #16AWG SHIELDED
TYPE TC - SUNLIGHT RESISTANT,DIRECT BURIAL
TFN CONDUCTORS, PVC JACKET, 600VOLTS,UL 1277
Click  for Printer Friendly Spec Sheet. | Construction: |
| CONDUCTOR: |
7 STRANDED BARE COPPER PER ASTM B-3. |
| INSULATION: |
POLYVINYLCHLORIDE WITH NYLON JACKET TYPE TFN PER UL 62 (GASOLINE AND OIL RESISTANT) |
| CONDUCTOR IDENTIFICATION: |
INSULATED CONDUCTORS ARE COLOR CODED PER ICEA METHOD 1 TABLE K-2 OF ICEA S-73-532 (FORMERLY K-2).* |
| ASSEMBLY: |
CONDUCTORS ARE TWISTED TOGETHER WITH ALUMINUM/MYLAR TAPE SHIELD AND STRANDED TINNED COPPER DRAIN WIRE TO PROVIDE 100% SHIELDING COVERAGE. |
| OVERALL JACKET: |
SUNLIGHT RESISTANT, FLAME RETARDANT, BLACK PVC PER UL 1277, WHICH PROTECTS AGAINST HEAT, FLAME, CHEMICALS, MOISTURE, AND MECHANICAL DAMAGE. |
| Charlotte Wire Part#* ↑ |
Size AWG |
Number of Conductors |
Insulation Thickness (in.) |
Nylon Thickness (in.) |
Jacket Thickness (in.) |
Overall Diameter (in.) |
Approx. Net Wt. (Lbs/Mft) |
Add to Quote Cart |
| CW02163 |
16 |
9 |
0.015 |
0.004 |
0.045 |
.48" |
139 |
|
| CW02162 |
16 |
37 |
0.015 |
0.004 |
0.08 |
.88" |
548 |
|
| CW02161 |
16 |
25 |
0.015 |
0.004 |
0.06 |
.73" |
365 |
|
| CW02160 |
16 |
19 |
0.015 |
0.004 |
0.06 |
.63" |
285 |
|
| CW02159 |
16 |
12 |
0.015 |
0.004 |
0.045 |
.52" |
180 |
|
| CW02158 |
16 |
10 |
0.015 |
0.004 |
0.045 |
.50" |
154 |
|
| CW02157 |
16 |
8 |
0.015 |
0.004 |
0.045 |
.43" |
126 |
|
| CW02156 |
16 |
7 |
0.015 |
0.004 |
0.045 |
.40" |
112 |
|
| CW02155 |
16 |
6 |
0.015 |
0.004 |
0.045 |
.40" |
100 |
|
| CW02154 |
16 |
5 |
0.015 |
0.004 |
0.045 |
.37" |
87 |
|
| CW02153 |
16 |
4 |
0.015 |
0.004 |
0.045 |
.34" |
73 |
|
| CW02152 |
16 |
3 |
0.015 |
0.004 |
0.045 |
.32" |
59 |
|
| CW02151 |
16 |
2 |
0.015 |
0.004 |
0.045 |
.31" |
45 |
|
| Displaying 1 to 13 (of 13 products) |
Result Pages: 1 |
| * To specify Method 1 Table E-1(formerly K-1), add suffix "M1" to Charlotte Wire Part Number. |
| Application |
| Control, Instrumentation, Signal or Lighting circuits rated 600Volts or less where circuit protection from ambient electrical interference is needed. |
| May be used as sunlight resistant, directly buried, and wet or dry locations. |
| Per NEC Articles 336 and 392, approved for installation in |
| 1) raceways and cable tray systems including ladders, troughs, channels, solid bottom trays, and other similar structures, |
| 2) lighting, control, and signal circuits |
| 3) aerial locations where supported by a messenger wire |
| 4) hazardous locations per Art.501 Class 1 Division 2, and |
| 5) Class 1 circuits as permitted in Article 725-21(B). |
| Standards |
| UL Standard 1277 for Type TC Cables |
| Passes UL and IEEE383 70,000BTU Flame Test. |
| UL Standard 62 for TFN Conductors |
| NEC Articles 336 and 392 for Tray Cable uses and constructions. |
|