VNTC TRAY CABLE - #14AWG SHIELDED
TYPE TC - SUNLIGHT RESISTANT,DIRECT BURIAL
THHN CONDUCTORS, PVC JACKET, 600VOLTS, UL 1277
| Construction: |
| CONDUCTOR: |
7 STRANDED BARE COPPER PER ASTM B-3. |
| INSULATION: |
POLYVINYLCHLORIDE WITH NYLON JACKET TYPE THHN/THWN PER UL 83 (GASOLINE AND OIL RESISTANT) |
| CONDUCTOR IDENTIFICATION: |
INSULATED CONDUCTORS ARE COLOR CODED PER ICEA METHOD 1 TABLE E-2 OF ICEA S-73-532 (FORMERLY K-2).* |
| ASSEMBLY: |
CONDUCTORS ARE TWISTED TOGETHER WITH ALUMINUM/MYLAR TAPE SHIELD AND STRANDED TINNED COPPER DRAIN WIRE TO PROVIDE 100% SHIELDING COVERAGE. |
| OVERALL JACKET: |
SUNLIGHT RESISTANT, FLAME RETARDANT BLACK PVC PER UL 1277, WHICH PROTECTS AGAINST HEAT, FLAME, CHEMICALS, MOISTURE, AND MECHANICAL DAMAGE. |
| Charlotte Wire Part#* ↑ |
Size AWG |
Number of Conductors |
Insulation Thickness (in.) |
Nylon Thickness (in.) |
Jacket Thickness (in.) |
Overall Diameter (in.) |
Approx. Net Wt. (Lbs/Mft) |
Add to Quote Cart |
| CW02259 |
14 |
37 |
0.015 |
0.004 |
0.08 |
.98" |
780 |
|
| CW02258 |
14 |
19 |
0.015 |
0.004 |
0.06 |
.71" |
405 |
|
| CW02257 |
14 |
12 |
0.015 |
0.004 |
0.06 |
.61" |
272 |
|
| CW02256 |
14 |
9 |
0.015 |
0.004 |
0.045 |
.55" |
212 |
|
| CW02255 |
14 |
7 |
0.015 |
0.004 |
0.045 |
.45" |
158 |
|
| CW02254 |
14 |
5 |
0.015 |
0.004 |
0.045 |
.41" |
121 |
|
| CW02253 |
14 |
4 |
0.015 |
0.004 |
0.045 |
.38" |
101 |
|
| CW02252 |
14 |
3 |
0.015 |
0.004 |
0.045 |
.35" |
81 |
|
| CW02251 |
14 |
2 |
0.015 |
0.004 |
0.045 |
.33" |
62 |
|
| Displaying 1 to 9 (of 9 products) |
Result Pages: 1 |
| * To specify ICEA Method 1 Table E-1(formerly K-1), add suffix "M1" to Charlotte Wire Part Number. |
| Application |
| Control, Instrumentation, signal, or Lighting circuits rated 600Volts or less where circuit protection from ambient electrical interference is needed. |
| May be used as sunlight resistant, directly buried, and wet or dry locations. |
| Per NEC Articles 336 and 392, approved for installation in |
| 1) raceways and cable tray systems including ladders, troughs, channels, solid bottom trays, and other similar structures, |
| 2) lighting, control, and signal circuits |
| 3) aerial locations where supported by a messenger wire |
| 4) hazardous locations per Art.501 Class 1 Division 2, and |
| 5) Class 1 circuits as permitted in Article 725-21(B). |
| Standards |
| UL Standard 1277 for Type TC Cables. |
| Passes UL and IEEE383 70,000BTU Flame Test. |
| UL Standard 83 for THHN Conductors. |
| NEC Articles 336 and 392 for Tray Cable uses and constructions. |
|
|