VNTC TRAY CABLE - #14AWG SHIELDED
TYPE TC - SUNLIGHT RESISTANT,DIRECT BURIAL
THHN CONDUCTORS, PVC JACKET, 600VOLTS, UL 1277

Construction:
CONDUCTOR: 7 STRANDED BARE COPPER PER ASTM B-3.
INSULATION: POLYVINYLCHLORIDE WITH NYLON JACKET TYPE THHN/THWN PER UL 83 (GASOLINE AND OIL RESISTANT)
CONDUCTOR IDENTIFICATION: INSULATED CONDUCTORS ARE COLOR CODED PER ICEA METHOD 1 TABLE E-2 OF ICEA S-73-532 (FORMERLY K-2).*
ASSEMBLY: CONDUCTORS ARE TWISTED TOGETHER WITH ALUMINUM/MYLAR TAPE SHIELD AND STRANDED TINNED COPPER DRAIN WIRE TO PROVIDE 100% SHIELDING COVERAGE.
OVERALL JACKET: SUNLIGHT RESISTANT, FLAME RETARDANT BLACK PVC PER UL 1277, WHICH PROTECTS AGAINST HEAT, FLAME, CHEMICALS, MOISTURE, AND MECHANICAL DAMAGE.
 Charlotte Wire Part#* ↑   Size AWG   Number of Conductors   Insulation Thickness (in.)   Nylon Thickness (in.)   Jacket Thickness (in.)   Overall Diameter (in.)   Approx. Net Wt. (Lbs/Mft)   Add to Quote Cart 
CW02259 14 37 0.015 0.004 0.08 .98" 780 Request Quote For This Product 
CW02258 14 19 0.015 0.004 0.06 .71" 405 Request Quote For This Product 
CW02257 14 12 0.015 0.004 0.06 .61" 272 Request Quote For This Product 
CW02256 14 9 0.015 0.004 0.045 .55" 212 Request Quote For This Product 
CW02255 14 7 0.015 0.004 0.045 .45" 158 Request Quote For This Product 
CW02254 14 5 0.015 0.004 0.045 .41" 121 Request Quote For This Product 
CW02253 14 4 0.015 0.004 0.045 .38" 101 Request Quote For This Product 
CW02252 14 3 0.015 0.004 0.045 .35" 81 Request Quote For This Product 
CW02251 14 2 0.015 0.004 0.045 .33" 62 Request Quote For This Product 
Displaying 1 to 9 (of 9 products) Result Pages:  1 
* To specify ICEA Method 1 Table E-1(formerly K-1), add suffix "M1" to Charlotte Wire Part Number.
Application
Control, Instrumentation, signal, or Lighting circuits rated 600Volts or less where circuit protection from ambient electrical interference is needed.
May be used as sunlight resistant, directly buried, and wet or dry locations.
Per NEC Articles 336 and 392, approved for installation in
1) raceways and cable tray systems including ladders, troughs, channels, solid bottom trays, and other similar structures,
2) lighting, control, and signal circuits
3) aerial locations where supported by a messenger wire
4) hazardous locations per Art.501 Class 1 Division 2, and
5) Class 1 circuits as permitted in Article 725-21(B).
Standards
UL Standard 1277 for Type TC Cables.
Passes UL and IEEE383 70,000BTU Flame Test.
UL Standard 83 for THHN Conductors.
NEC Articles 336 and 392 for Tray Cable uses and constructions.