VNTC TRAY CABLE - #10AWG NONSHIELDED
TYPE TC - SUNLIGHT RESISTANT,DIRECT BURIAL
THHN CONDUCTORS, PVC JACKET, 600VOLTS, UL 1277
Click  for Printer Friendly Spec Sheet. | Construction: |
| CONDUCTOR: |
7 STRANDED BARE COPPER PER ASTM B-3.
|
| INSULATION: |
POLYVINYLCHLORIDE WITH NYLON JACKET TYPE THHN/THWN PER UL 83 (GASOLINE AND OIL RESISTANT)
|
| CONDUCTOR IDENTIFICATION: |
INSULATED CONDUCTORS ARE COLOR CODED ICEA METHOD 1 TABLE E-2 OF ICEA S-73-532 (FORMERLY K-2).*
|
| ASSEMBLY: |
CONDUCTORS ARE CABLED TOGETHER WITH A SUITABLE TAPE SEPARATOR AS NEEDED.
|
| OVERALL JACKET: |
SUNLIGHT RESISTANT, FLAME RETARDANT BLACK PVC PER UL1277, WHICH PROTECTS AGAINST HEAT, FLAME, CHEMICALS, MOISTURE, AND MECHANICAL DAMAGE.
|
| Charlotte Wire Part# ↓ |
Size AWG |
Number of Conductors |
Insulation Thickness (in.) |
Nylon Thickness (in.) |
Jacket Thickness (in.) |
Overall Diameter (in.) |
Approx. Net Wt. (Lbs/Mft) |
Add to Quote Cart |
| CW02326 |
10 |
2 |
0.02 |
0.004 |
0.045 |
.26" x .43"** |
114 |
|
| CW02327 |
10 |
3 |
0.02 |
0.004 |
0.045 |
.46" |
157 |
|
| CW02328 |
10 |
4 |
0.02 |
0.004 |
0.045 |
.50" |
201 |
|
| CW02329 |
10 |
5 |
0.02 |
0.004 |
0.06 |
.58" |
264 |
|
| CW02330 |
10 |
7 |
0.02 |
0.004 |
0.06 |
.63" |
348 |
|
| CW02331 |
10 |
9 |
0.02 |
0.004 |
0.06 |
.73" |
443 |
|
| CW02332 |
10 |
12 |
0.02 |
0.004 |
0.06 |
.82" |
575 |
|
| CW02333 |
10 |
19 |
0.02 |
0.004 |
0.08 |
1.00" |
910 |
|
| Displaying 1 to 8 (of 8 products) |
Result Pages: 1 |
| *To specify Method 1 Table E-1(formerly K-1), add suffix "M1" to Charlotte Wire Part Number.
|
| ** Flat Construction
|
| Application |
| Control, Signal, or Lighting circuits rated 600Volts.
|
| May be used as sunlight resistant, directly buried, and wet or dry locations.
|
| Per NEC Articles 336 and 392, approved for installation in
|
| 1) raceways and cable tray systems including ladders, troughs, channels, solid bottom trays, and other similar structures,
|
| 2) lighting, control, and signal circuits
|
| 3) aerial locations where supported by a messenger wire
|
| 4) hazardous locations per Art.501 Class 1 Division 2, and
|
| 5) Class 1 circuits as permitted in Article 725-21(B).
|
| Standards |
| UL Standard 1277 for Type TC Cables.
|
| Passes UL and IEEE383 70,000BTU Flame Test.
|
| UL Standard 83 for THHN Conductors.
|
| NEC Articles 336 and 392 for Tray Cable uses and constructions.
|
|