VNTC TRAY CABLE- 4 CONDUCTOR W/GROUND
TYPE TC - SUNLIGHT RESISTANT, DIRECT BURIAL
THHN CONDUCTORS, PVC JACKET, 600VOLTS, UL 1277
Click  for Printer Friendly Spec Sheet. | Construction: |
| CONDUCTOR: |
CLASS B STRANDED BARE COPPER PER ASTM B-3.
|
| INSULATION: |
POLYVINYLCHLORIDE WITH NYLON JACKET TYPE THHN/THWN PER UL 83 (GASOLINE AND OIL RESISTANT)
|
| CONDUCTOR IDENTIFICATION: |
INSULATED CONDUCTORS COLOR CODED PER ICEA METHOD 4 (BLACK CONDUCTORS WITH PRINTED NUMBERS)
|
| ASSEMBLY: |
CONDUCTORS CABLED TOGETHER WITH A STRANDED COPPER GROUND WIRE IN ONE OF THE INTERSTICES, SUITABLE FILLERS FOR ROUNDNESS WHERE NEEDED, AND CABLE TAPE.
|
| OVERALL JACKET: |
SUNLIGHT RESISTANT, FLAME RETARDANT BLACK PVC PER UL 1277, WHICH PROTECTS AGAINST HEAT, FLAME, CHEMICALS, MOISTURE, AND MECHANICAL DAMAGE.
|
| Charlotte Wire Part# ↓ |
4 Cond'r Cable Size |
Number of Strands |
Insulation Thickness (in.) PVC |
Insulation Thickness (in.) Nylon |
Jacket Thickness (in.) |
Ground Wire Size* (AWG) |
Overall Diameter (in.) |
Approx. Net Wt. (Lbs/Mft) |
Add to Quote Cart |
| CW02425 |
8 |
7 |
0.03 |
0.005 |
0.06 |
10 |
.67" |
369 |
|
| CW02426 |
6 |
7 |
0.03 |
0.005 |
0.06 |
8 |
.75" |
545 |
|
| CW02427 |
4 |
7 |
0.04 |
0.006 |
0.08 |
8 |
.96" |
842 |
|
| CW02428 |
2 |
7 |
0.04 |
0.006 |
0.08 |
6 |
1.11" |
1235 |
|
| CW02429 |
1 |
19 |
0.05 |
0.007 |
0.08 |
6 |
1.26" |
1530 |
|
| CW02430 |
1/0 |
19 |
0.05 |
0.007 |
0.08 |
6 |
1.35" |
1860 |
|
| CW02431 |
2/0 |
19 |
0.05 |
0.007 |
0.08 |
6 |
1.46" |
2232 |
|
| CW02432 |
3/0 |
19 |
0.05 |
0.007 |
0.08 |
4 |
1.58" |
2810 |
|
| CW02433 |
4/0 |
19 |
0.05 |
0.007 |
0.11 |
4 |
1.77" |
3475 |
|
| CW02434 |
250MCM |
37 |
0.06 |
0.008 |
0.11 |
4 |
1.94" |
4080 |
|
| CW02435 |
350MCM |
37 |
0.06 |
0.008 |
0.11 |
3 |
2.19" |
5560 |
|
| CW02436 |
500MCM |
37 |
0.06 |
0.008 |
0.11 |
2 |
2.50" |
7620 |
|
| CW02437 |
750MCM |
61 |
0.07 |
0.009 |
0.14 |
1 |
3.10" |
11510 |
|
| Displaying 1 to 13 (of 13 products) |
Result Pages: 1 |
| * Also available with 2 grounds in each of two opposite interstices.
|
| Application |
| Power circuits rated 600Volts, 90°C in dry locations and 75°C in wet locations.
|
| Per NEC Articles 336 and 392, approved for installation in
|
| 1) raceways and cable tray systems including ladders, troughs, channels, solid bottom trays, and other similar structures,
|
| 2) aerial locations where supported by a messenger wire,
|
| 3) hazardous locations per Art.501 Class 1 Division 2.
|
| Standards |
| UL Standard 1277 for Type TC Cables.
|
| Passes UL and IEEE383 70,000BTU Flame Test.
|
| UL Standard 83 for THHN Conductors.
|
| NEC Articles 336 & 392 for Tray Cable uses and constructions.
|
|