SHIELDED TRAY CABLE 3/C & 4/C W/GND
TYPE TC - SUNLIGHT RESISTANT, DIRECT BURIAL
THHN CONDUCTORS, PVC JACKET, 600VOLTS, UL 1277
| Construction: |
| CONDUCTOR: |
CLASS B STRANDED BARE COPPER PER ASTM B-3.
|
| INSULATION: |
POLYVINYLCHLORIDE WITH NYLON JACKET TYPE THHN/THWN PER UL 83 (GASOLINE AND OIL RESISTANT)
|
| CONDUCTOR IDENTIFICATION: |
INSULATED CONDUCTORS COLOR CODED PER ICEA METHOD 4 (BLACK CONDUCTORS WITH PRINTED NUMBERS)
|
| GROUND WIRE: |
CONDUCTORS CABLED TOGETHER WITH A STRANDED COPPER GROUND WIRE IN ONE OF THE INTERSTICES.
|
| SHIELD: |
5MIL COPPER TAPE SPIRALLY APPLIED OVER CONDUCTOR ASSEMBLY.
|
| OVERALL JACKET: |
SUNLIGHT RESISTANT, FLAME RETARDANT BLACK PVC PER UL 1277, WHICH PROTECTS AGAINST HEAT, FLAME, CHEMICALS, MOISTURE, AND MECHANICAL DAMAGE.
|
| Charlotte Wire Part# ↑ |
Size AWG |
Number of Cond'rs |
Insulation Thickness (in.) PVC |
Insulation Thickness (in.) Nylon |
Jacket Thickness (in.) |
Ground Wire Size (AWG) |
Overall Diameter (in.) |
Approx. Net Wt. (Lbs/Mft) |
Add to Quote Cart |
| CW02448 |
2 |
4 |
0.05 |
0.007 |
0.08 |
6 |
1.15" |
1190 |
|
| CW02447 |
2 |
3 |
0.05 |
0.007 |
0.08 |
6 |
1.04" |
1060 |
|
| CW02446 |
4 |
4 |
0.05 |
0.007 |
0.08 |
6 |
1.00" |
860 |
|
| CW02445 |
4 |
3 |
0.05 |
0.007 |
0.08 |
6 |
.91" |
730 |
|
| CW02444 |
6 |
4 |
0.04 |
0.006 |
0.06 |
8 |
.78" |
600 |
|
| CW02443 |
6 |
3 |
0.04 |
0.006 |
0.06 |
8 |
.72" |
490 |
|
| CW02442 |
8 |
4 |
0.03 |
0.005 |
0.06 |
10 |
.68" |
430 |
|
| CW02441 |
8 |
3 |
0.03 |
0.005 |
0.06 |
10 |
.64" |
350 |
|
| Displaying 1 to 8 (of 8 products) |
Result Pages: 1 |
| Application |
| Power circuits rated 600Volts, 90°C in dry locations and 75°C in wet locations.
|
| Per NEC Articles 336 and 392, approved for installation in
|
| 1) raceways and cable tray systems including ladders, troughs, channels, solid bottom trays, and other similar structures,
|
| 2) aerial locations where supported by a messenger wire,
|
| 3) hazardous locations per Art.501 Class 1 Division 2.
|
| Standards |
| UL Standard 1277 for Type TC Cables.
|
| Passes UL and IEEE383 70,000BTU Flame Test.
|
| UL Standard 83 for THHN Conductors.
|
| NEC Articles 336 & 392 for Tray Cable uses and constructions.
|
|
|