XLP/PVC TRAY CABLE - #14AWG
TYPE TC - SUNLIGHT RESISTANT,DIRECT BURIAL
XHHW-2 VW1 CONDUCTORS, PVC JACKET, 600VOLTS

Construction:
CONDUCTOR: 7 STRANDED BARE COPPER PER ASTM B-3.
INSULATION: FLAME-RETARDANT CROSSLINKED POLYETHYLENE (XLP) TYPE XHHW-2 VW1 PER UL 44. INSULATED CONDUCTORS RATED 90°C WET OR DRY.
CONDUCTOR IDENTIFICATION: INSULATED CONDUCTORS ARE COLOR CODED PER ICEA METHOD 1 TABLE E-2 OF ICEA S-73-532. (FORMERLY K-2).*
ASSEMBLY: CONDUCTORS ARE CABLED TOGETHER WITH A SUITABLE TAPE SEPARATOR AS NEEDED.
OVERALL JACKET: SUNLIGHT RESISTANT, FLAME RETARDANT BLACK PVC PER UL1277, WHICH PROTECTS AGAINST HEAT, FLAME, CHEMICALS, MOISTURE, AND MECHANICAL DAMAGE.
 Charlotte Wire Part# ↑   Size AWG   Number of Conductors   Insulation Thickness (in.)   Jacket Thickness (in.)   Overall Diameter (in.)   Approx. Net Wt. (Lbs/Mft)   Add to Quote Cart 
CW02484 14 37 0.03 0.08 1.14" 890 Request Quote For This Product 
CW02483 14 30 0.03 0.08 1.08" 740 Request Quote For This Product 
CW02482 14 25 0.03 0.08 1.00" 635 Request Quote For This Product 
CW02481 14 20 0.03 0.06 .90" 505 Request Quote For This Product 
CW02480 14 19 0.03 0.06 .82" 458 Request Quote For This Product 
CW02479 14 15 0.03 0.06 .77" 366 Request Quote For This Product 
CW02478 14 12 0.03 0.06 .72" 305 Request Quote For This Product 
CW02477 14 10 0.03 0.06 .69" 268 Request Quote For This Product 
CW02476 14 9 0.03 0.06 .64" 240 Request Quote For This Product 
CW02475 14 7 0.03 0.045 .52" 181 Request Quote For This Product 
CW02474 14 5 0.03 0.045 .48" 142 Request Quote For This Product 
CW02473 14 4 0.03 0.045 .44" 118 Request Quote For This Product 
CW02472 14 3 0.03 0.045 .40" 93 Request Quote For This Product 
CW02471 14 2 0.03 0.045 .24" x .38"** 72 Request Quote For This Product 
Displaying 1 to 14 (of 14 products) Result Pages:  1 
*To specify Method 1 Table E-1(formerly K-1), add suffix "M1" to Charlotte Wire Part Number.
**Flat Construction
Application
Control, signal, or lighting circuits rated 600Volts
where a high temperature, low dielectric loss insulation is needed.
May be used as sunlight resistant, directly buried, and wet or dry
locations.
Per NEC Articles 336 and 392, approved for installation in
1) raceways and cable tray systems including ladders, troughs, channels, solid bottom trays, and other similar structures,
2) lighing, control, and signal circuits,
3) aerial locations where supported by a messenger wire,
4) hazardous locations per NEC Article 501 Class 1 Division 2, and
5) Class 1 circuits as permitted in Article 725-21(B).
Standards
UL Standard 1277 for Type TC cables.
Passes UL and IEEE383 70,000 BTU flame test.
UL Standard 44 for XHHW-2 C'drs.
ICEA S-95-658/NEMA WC70 for Nonshielded 0-2kv Cables. (Formerly ICEA S-66-524/NEMA WC7)
NEC Articles 336 & 392 for Tray cable uses and constructions.