XLP/PVC TRAY CABLE - #10AWG
TYPE TC - SUNLIGHT RESISTANT,DIRECT BURIAL
XHHW-2 VW1 CONDUCTORS, PVC JACKET, 600VOLTS
Click  for Printer Friendly Spec Sheet. | Construction: |
| CONDUCTOR: |
7 STRANDED BARE COPPER PER ASTM B-3.
|
| INSULATION: |
FLAME-RETARDANT CROSSLINKED POLYETHYLENE (XLP) TYPE XHHW-2 VW1 PER UL 44.
|
| INSULATED CONDUCTORS RATED 90°C WET OR DRY.
|
| CONDUCTOR IDENTIFICATION: |
INSULATED CONDUCTORS ARE COLOR CODED PER ICEA METHOD 1 TABLE E-2 OF ICEA S-73-532. (FORMERLY K-2).*
|
| ASSEMBLY: |
CONDUCTORS ARE CABLED TOGETHER WITH A SUITABLE TAPE SEPARATOR AS NEEDED.
|
| OVERALL JACKET: |
SUNLIGHT RESISTANT, FLAME RETARDANT BLACK PVC PER UL1277, WHICH PROTECTS AGAINST HEAT, FLAME, CHEMICALS, MOISTURE, AND MECHANICAL DAMAGE.
|
| Charlotte Wire Part# ↓ |
Size AWG |
Number of Conductors |
Insulation Thickness (in.) |
Jacket Thickness (in.) |
Overall Diameter (in.) |
Approx. Net Wt. (Lbs/Mft) |
Add to Quote Cart |
| CW02511 |
10 |
2 |
0.03 |
0.045 |
.28" x .46"** |
130 |
|
| CW02512 |
10 |
3 |
0.03 |
0.045 |
.49" |
175 |
|
| CW02513 |
10 |
4 |
0.03 |
0.045 |
.56" |
230 |
|
| CW02514 |
10 |
5 |
0.03 |
0.06 |
.63" |
285 |
|
| CW02515 |
10 |
7 |
0.03 |
0.06 |
.69" |
381 |
|
| CW02516 |
10 |
9 |
0.03 |
0.06 |
.80" |
480 |
|
| CW02517 |
10 |
12 |
0.03 |
0.08 |
.94" |
637 |
|
| CW02518 |
10 |
19 |
0.03 |
0.08 |
1.09" |
955 |
|
| CW02519 |
10 |
25 |
0.03 |
0.08 |
1.26" |
1230 |
|
| CW02520 |
10 |
37 |
0.03 |
0.08 |
1.44" |
1770 |
|
| Displaying 1 to 10 (of 10 products) |
Result Pages: 1 |
| *To specify Method 1 Table E-1(formerly K-1), add suffix "M1" to Charlotte Wire Part Number.
|
| **Flat Construction
|
| Application |
| Control, signal, or lighting circuits rated 600Volts
|
| where a high temperature, low dielectric loss insulation is needed.
|
| May be used as sunlight resistant, directly buried, and wet or dry
|
| locations.
|
| Per NEC Articles 336 and 392, approved for installation in
|
| 1) raceways and cable tray systems including ladders, troughs, channels, solid bottom trays, and other similar structures,
|
| 2) lighing, control, and signal circuits,
|
| 3) aerial locations where supported by a messenger wire,
|
| 4) hazardous locations per NEC Article 501 Class 1 Division 2, and
|
| 5) Class 1 circuits as permitted in Article 725-21(B).
|
| Standards |
| UL Standard 1277 for Type TC.
|
| Passes UL and IEEE383 70,000 BTU flame test.
|
| UL Standard 44 for XHHW-2 conductors.
|
| ICEA S-95-658/NEMA WC70 for Nonshielded 0-2kv Cables. (Formerly ICEA S-66-524/ NEMA WC7).
|
| NEC Articles 336 & 392 for Tray cable uses and constructions.
|
|