XLP/PVC TRAY CABLE - #10AWG
TYPE TC - SUNLIGHT RESISTANT,DIRECT BURIAL
XHHW-2 VW1 CONDUCTORS, PVC JACKET, 600VOLTS

Construction:
CONDUCTOR: 7 STRANDED BARE COPPER PER ASTM B-3.
INSULATION: FLAME-RETARDANT CROSSLINKED POLYETHYLENE (XLP) TYPE XHHW-2 VW1 PER UL 44.
INSULATED CONDUCTORS RATED 90°C WET OR DRY.
CONDUCTOR IDENTIFICATION: INSULATED CONDUCTORS ARE COLOR CODED PER ICEA METHOD 1 TABLE E-2 OF ICEA S-73-532. (FORMERLY K-2).*
ASSEMBLY: CONDUCTORS ARE CABLED TOGETHER WITH A SUITABLE TAPE SEPARATOR AS NEEDED.
OVERALL JACKET: SUNLIGHT RESISTANT, FLAME RETARDANT BLACK PVC PER UL1277, WHICH PROTECTS AGAINST HEAT, FLAME, CHEMICALS, MOISTURE, AND MECHANICAL DAMAGE.
 Charlotte Wire Part# ↓   Size AWG   Number of Conductors   Insulation Thickness (in.)   Jacket Thickness (in.)   Overall Diameter (in.)   Approx. Net Wt. (Lbs/Mft)   Add to Quote Cart 
CW02511 10 2 0.03 0.045 .28" x .46"** 130 Request Quote For This Product 
CW02512 10 3 0.03 0.045 .49" 175 Request Quote For This Product 
CW02513 10 4 0.03 0.045 .56" 230 Request Quote For This Product 
CW02514 10 5 0.03 0.06 .63" 285 Request Quote For This Product 
CW02515 10 7 0.03 0.06 .69" 381 Request Quote For This Product 
CW02516 10 9 0.03 0.06 .80" 480 Request Quote For This Product 
CW02517 10 12 0.03 0.08 .94" 637 Request Quote For This Product 
CW02518 10 19 0.03 0.08 1.09" 955 Request Quote For This Product 
CW02519 10 25 0.03 0.08 1.26" 1230 Request Quote For This Product 
CW02520 10 37 0.03 0.08 1.44" 1770 Request Quote For This Product 
Displaying 1 to 10 (of 10 products) Result Pages:  1 
*To specify Method 1 Table E-1(formerly K-1), add suffix "M1" to Charlotte Wire Part Number.
**Flat Construction
Application
Control, signal, or lighting circuits rated 600Volts
where a high temperature, low dielectric loss insulation is needed.
May be used as sunlight resistant, directly buried, and wet or dry
locations.
Per NEC Articles 336 and 392, approved for installation in
1) raceways and cable tray systems including ladders, troughs, channels, solid bottom trays, and other similar structures,
2) lighing, control, and signal circuits,
3) aerial locations where supported by a messenger wire,
4) hazardous locations per NEC Article 501 Class 1 Division 2, and
5) Class 1 circuits as permitted in Article 725-21(B).
Standards
UL Standard 1277 for Type TC.
Passes UL and IEEE383 70,000 BTU flame test.
UL Standard 44 for XHHW-2 conductors.
ICEA S-95-658/NEMA WC70 for Nonshielded 0-2kv Cables. (Formerly ICEA S-66-524/ NEMA WC7).
NEC Articles 336 & 392 for Tray cable uses and constructions.