XLP/PVC TRAY CABLE 3CONDUCTOR W/GND
TYPE TC - SUNLIGHT RESISTANT,DIRECT BURIAL
XHHW-2 CONDUCTORS, PVC JACKET, 600VOLTS
Click  for Printer Friendly Spec Sheet. | Construction: |
| CONDUCTOR: |
CLASS B STRANDED BARE COPPER PER ASTM B-3.
|
| INSULATION: |
FLAME-RETARDANT CROSSLINKED POLYETHYLENE (XLP) TYPE XHHW-2 PER UL 44. CONDUCTORS RATED 90°C WET OR DRY.
|
| CONDUCTOR IDENTIFICATION: |
INSULATED CONDUCTORS COLOR CODED PER ICEA METHOD 4 (BLACK WITH PRINTED NUMBERS) ON #8 AND LARGER. SIZES #14 THROUGH #10 COLOR CODED PER ICEA METHOD 1 TABLE E-2 (BLACK-RED-BLUE)*.
|
| ASSEMBLY: |
CONDUCTORS CABLED TOGETHER WITH A STRANDED COPPER GROUND WIRE IN ONE OF THE INTERSTICES, SUITABLE FILLERS FOR ROUNDNESS WHERE NEEDED, AND CABLE TAPE.
|
| OVERALL JACKET: |
SUNLIGHT RESISTANT, FLAME RETARDANT BLACK PVC PER UL1277, WHICH PROTECTS AGAINST HEAT, FLAME, CHEMICALS, MOISTURE, AND MECHANICAL DAMAGE.
|
| Charlotte Wire Part# ↓ |
Size AWG |
Number of Conductors |
Insulation Thickness (in.) |
Jacket Thickness (in.) |
Ground Wire Size (AWG) |
Overall Diameter (in.) |
Approx. Net Wt. (Lbs/Mft) |
Add to Quote Cart |
| CW02530 |
14 |
3 |
0.03 |
0.045 |
14 |
.39" |
110 |
|
| CW02531 |
12 |
3 |
0.03 |
0.045 |
12 |
.43" |
152 |
|
| CW02532 |
10 |
3 |
0.03 |
0.045 |
10 |
.49" |
210 |
|
| CW02533 |
8 |
3 |
0.045 |
0.06 |
10 |
.68" |
336 |
|
| CW02534 |
6 |
3 |
0.045 |
0.06 |
8 |
.76" |
460 |
|
| CW02535 |
4 |
3 |
0.045 |
0.08 |
8 |
.88" |
695 |
|
| CW02536 |
2 |
3 |
0.045 |
0.08 |
6 |
1.02" |
990 |
|
| CW02537 |
1 |
3 |
0.055 |
0.08 |
6 |
1.16" |
1278 |
|
| CW02538 |
1/0 |
3 |
0.055 |
0.08 |
6 |
1.23" |
1464 |
|
| CW02539 |
2/0 |
3 |
0.055 |
0.08 |
6 |
1.33" |
1775 |
|
| CW02540 |
3/0 |
3 |
0.055 |
0.08 |
4 |
1.45" |
2180 |
|
| CW02541 |
4/0 |
3 |
0.055 |
0.08 |
4 |
1.57" |
2640 |
|
| CW02542 |
250MCM |
3 |
0.065 |
0.11 |
4 |
1.76" |
3240 |
|
| CW02543 |
350MCM |
3 |
0.065 |
0.11 |
3 |
2.00" |
4330 |
|
| CW02544 |
500MCM |
3 |
0.065 |
0.11 |
2 |
2.28" |
6120 |
|
| CW02546 |
600MCM |
3 |
0.08 |
0.11 |
2 |
2.60" |
8290 |
|
| CW02547 |
750MCM |
3 |
0.08 |
0.11 |
1 |
2.84" |
9010 |
|
| CW02548 |
1000MCM |
3 |
0.08 |
0.14 |
1/0 |
3.20" |
12985 |
|
| Displaying 1 to 18 (of 18 products) |
Result Pages: 1 |
| * All sizes may also be coded by means of black conductors and stripe painted phase colors.(Black-Red-Blue)
|
| Application |
| Power circuits rated 600volts where a high temperature, low dielectric loss insulation is needed.
|
| May be used as sunlight resistant, directly buried, and wet or dry locations.
|
| Per NEC Articles 336 and 392, approved for installation in
|
| 1)raceways and cable tray systems including ladders, troughs, channels, solid bottom trays, and other similar structures,
|
| 2) aerial locations where supported by a messenger wire, and
|
| 3) hazardous locations per NEC Article 501 Class 1 Division 2.
|
| Standards |
| UL Standard 1277 for Type TC cables.
|
| Passes UL and IEEE383 70,000BTU flame test.
|
| UL Standard 44 for XHHW-2 conductors.
|
| ICEA S-95-658/NEMA WC70 for Nonshielded 0-2kv Cables. (Formerly ICEA S-66-524/NEMA WC7).
|
| NEC Articles 336 & 392 for Tray Cable uses and constructions.
|
|