XLP/PVC TRAY CABLE 3CONDUCTOR W/GND
TYPE TC - SUNLIGHT RESISTANT,DIRECT BURIAL
XHHW-2 CONDUCTORS, PVC JACKET, 600VOLTS

Construction:
CONDUCTOR: CLASS B STRANDED BARE COPPER PER ASTM B-3.
INSULATION: FLAME-RETARDANT CROSSLINKED POLYETHYLENE (XLP) TYPE XHHW-2 PER UL 44. CONDUCTORS RATED 90°C WET OR DRY.
CONDUCTOR IDENTIFICATION: INSULATED CONDUCTORS COLOR CODED PER ICEA METHOD 4 (BLACK WITH PRINTED NUMBERS) ON #8 AND LARGER. SIZES #14 THROUGH #10 COLOR CODED PER ICEA METHOD 1 TABLE E-2 (BLACK-RED-BLUE)*.
ASSEMBLY: CONDUCTORS CABLED TOGETHER WITH A STRANDED COPPER GROUND WIRE IN ONE OF THE INTERSTICES, SUITABLE FILLERS FOR ROUNDNESS WHERE NEEDED, AND CABLE TAPE.
OVERALL JACKET: SUNLIGHT RESISTANT, FLAME RETARDANT BLACK PVC PER UL1277, WHICH PROTECTS AGAINST HEAT, FLAME, CHEMICALS, MOISTURE, AND MECHANICAL DAMAGE.
 Charlotte Wire Part# ↓   Size AWG   Number of Conductors   Insulation Thickness (in.)   Jacket Thickness (in.)   Ground Wire Size (AWG)   Overall Diameter (in.)   Approx. Net Wt. (Lbs/Mft)   Add to Quote Cart 
CW02530 14 3 0.03 0.045 14 .39" 110 Request Quote For This Product 
CW02531 12 3 0.03 0.045 12 .43" 152 Request Quote For This Product 
CW02532 10 3 0.03 0.045 10 .49" 210 Request Quote For This Product 
CW02533 8 3 0.045 0.06 10 .68" 336 Request Quote For This Product 
CW02534 6 3 0.045 0.06 8 .76" 460 Request Quote For This Product 
CW02535 4 3 0.045 0.08 8 .88" 695 Request Quote For This Product 
CW02536 2 3 0.045 0.08 6 1.02" 990 Request Quote For This Product 
CW02537 1 3 0.055 0.08 6 1.16" 1278 Request Quote For This Product 
CW02538 1/0 3 0.055 0.08 6 1.23" 1464 Request Quote For This Product 
CW02539 2/0 3 0.055 0.08 6 1.33" 1775 Request Quote For This Product 
CW02540 3/0 3 0.055 0.08 4 1.45" 2180 Request Quote For This Product 
CW02541 4/0 3 0.055 0.08 4 1.57" 2640 Request Quote For This Product 
CW02542 250MCM 3 0.065 0.11 4 1.76" 3240 Request Quote For This Product 
CW02543 350MCM 3 0.065 0.11 3 2.00" 4330 Request Quote For This Product 
CW02544 500MCM 3 0.065 0.11 2 2.28" 6120 Request Quote For This Product 
CW02546 600MCM 3 0.08 0.11 2 2.60" 8290 Request Quote For This Product 
CW02547 750MCM 3 0.08 0.11 1 2.84" 9010 Request Quote For This Product 
CW02548 1000MCM 3 0.08 0.14 1/0 3.20" 12985 Request Quote For This Product 
Displaying 1 to 18 (of 18 products) Result Pages:  1 
* All sizes may also be coded by means of black conductors and stripe painted phase colors.(Black-Red-Blue)
Application
Power circuits rated 600volts where a high temperature, low dielectric loss insulation is needed.
May be used as sunlight resistant, directly buried, and wet or dry locations.
Per NEC Articles 336 and 392, approved for installation in
1)raceways and cable tray systems including ladders, troughs, channels, solid bottom trays, and other similar structures,
2) aerial locations where supported by a messenger wire, and
3) hazardous locations per NEC Article 501 Class 1 Division 2.
Standards
UL Standard 1277 for Type TC cables.
Passes UL and IEEE383 70,000BTU flame test.
UL Standard 44 for XHHW-2 conductors.
ICEA S-95-658/NEMA WC70 for Nonshielded 0-2kv Cables. (Formerly ICEA S-66-524/NEMA WC7).
NEC Articles 336 & 392 for Tray Cable uses and constructions.