XLP/PVC TRAY CABLE 4CONDUCTOR W/GND
TYPE TC - SUNLIGHT RESISTANT,DIRECT BURIAL
XHHW-2 CONDUCTORS, PVC JACKET, 600VOLTS
Click  for Printer Friendly Spec Sheet. | Construction: |
| CONDUCTOR: |
CLASS B STRANDED BARE COPPER PER ASTM B-3.
|
| INSULATION: |
FLAME-RETARDANT CROSSLINKED POLYETHYLENE (XLP) TYPE XHHW-2 PER UL 44. CONDUCTORS RATED 90°C WET OR DRY.
|
| CONDUCTOR IDENTIFICATION: |
INSULATED CONDUCTORS COLOR CODED PER ICEA METHOD 4 (BLACK CONDUCTORS WITH PRINTED NUMBERS).
|
| ALSO MAY BE CODED BY MEANS OF BLACK CONDUCTORS AND STRIPE PAINTED PHASE COLORS (BLACK-RED-BLUE-ORANGE).
|
| ASSEMBLY: |
CONDUCTORS CABLED TOGETHER WITH A STRANDED COPPER GROUND WIRE IN ONE OF THE INTERSTICES, SUITABLE FILLERS FOR ROUNDNESS WHERE NEEDED, AND CABLE TAPE.
|
| OVERALL JACKET: |
SUNLIGHT RESISTANT, FLAME RETARDANT BLACK PVC PER UL1277, WHICH PROTECTS AGAINST HEAT, FLAME, CHEMICALS, MOISTURE, AND MECHANICAL DAMAGE.
|
| Charlotte Wire Part# ↑ |
Size AWG |
Number of Conductors |
Insulation Thickness (in.) |
Jacket Thickness (in.) |
Ground Wire Size * (AWG) |
Overall Diameter (in.) |
Approx. Net Wt. (Lbs/Mft) |
Add to Quote Cart |
| CW02575 |
1000MCM |
4 |
0.08 |
0.14 |
1/0 |
3.50" |
16880 |
|
| CW02574 |
750MCM |
4 |
0.08 |
0.14 |
1 |
3.12" |
12200 |
|
| CW02573 |
600MCM |
4 |
0.08 |
0.14 |
2 |
2.85" |
10380 |
|
| CW02572 |
500MCM |
4 |
0.065 |
0.11 |
2 |
2.52" |
7750 |
|
| CW02571 |
350MCM |
4 |
0.065 |
0.11 |
3 |
2.21" |
5620 |
|
| CW02570 |
250MCM |
4 |
0.065 |
0.11 |
4 |
1.95" |
4185 |
|
| CW02569 |
4/0 |
4 |
0.055 |
0.11 |
4 |
1.80" |
3530 |
|
| CW02568 |
3/0 |
4 |
0.055 |
0.08 |
4 |
1.61" |
2860 |
|
| CW02567 |
2/0 |
4 |
0.055 |
0.08 |
6 |
1.47" |
2282 |
|
| CW02566 |
1/0 |
4 |
0.055 |
0.08 |
6 |
1.38" |
1892 |
|
| CW02565 |
1 |
4 |
0.055 |
0.08 |
6 |
1.28" |
1590 |
|
| CW02564 |
2 |
4 |
0.045 |
0.08 |
6 |
1.12" |
1270 |
|
| CW02563 |
4 |
4 |
0.045 |
0.08 |
8 |
.97" |
858 |
|
| CW02562 |
6 |
4 |
0.045 |
0.06 |
8 |
.81" |
585 |
|
| CW02561 |
8 |
4 |
0.045 |
0.06 |
10 |
.73" |
410 |
|
| Displaying 1 to 15 (of 15 products) |
Result Pages: 1 |
| * Also available with 2 grounds in each of two opposite interstices.
|
| Application |
| Power circuits rated 600volts where a high temperature, low dielectric loss insulation is needed.
|
| May be used as sunlight resistant, directly buried, and wet or dry locations.
|
| Per NEC Articles 336 and 392, approved for installation in
|
| 1) raceways and cable tray systems including ladders, troughs, channels, solid bottom trays, and other similar structures,
|
| 2) aerial locations where supported by a messenger wire, and
|
| 3) hazardous locations per NEC Article 501 Class 1 Division 2.
|
| Standards |
| UL Standard 1277 for Type TC cables.
|
| Passes UL and IEEE383 70,000BTU flame test.
|
| UL Standard 44 for XHHW-2 conductors.
|
| ICEA S-95-658/NEMA WC70 for Nonshielded 0-2kv Cables. (Formerly ICEA S-66-524/NEMA WC7).
|
| NEC Articles 336 & 392 for Tray Cable uses and constructions.
|
|