FREP/CPE TRAY CABLE - #14AWG
TYPE TC - SUNLIGHT RESISTANT,DIRECT BURIAL
XHHW-2 VW1 CONDUCTORS, CPE JACKET, 600VOLTS

Construction:
CONDUCTOR: 7 STRANDED TINNED COPPER.
INSULATION: THERMOSETTING FLAME-RETARDANT ETHYLENE PROPYLENE RUBBER TYPE XHHW-2 VW1 PER UL 44. INSULATED CONDUCTORS RATED 90°C WET OR DRY.
CONDUCTOR IDENTIFICATION: INSULATED CONDUCTORS ARE COLOR CODED PER ICEA METHOD 1 TABLE E-2 OF ICEA S-73-532 (FORMERLY K-2).*
ASSEMBLY: CONDUCTORS ARE CABLED TOGETHER WITH A SUITABLE TAPE SEPARATOR AS NEEDED.
OVERALL JACKET: SUNLIGHT RESISTANT, FLAME RETARDANT BLACK CPE PER UL 1277, WHICH PROTECTS AGAINST HEAT, FLAME, CHEMICALS, MOISTURE, AND MECHANICAL DAMAGE.
 Charlotte Wire Part#* ↓   Size AWG   Number of Conductors   Insulation Thickness (in.)   Jacket Thickness (in.)   Overall Diameter (in.)   Approx. Net Wt. (Lbs/Mft)   Add to Quote Cart 
CW02601 14 2 0.03 0.045 .25" x .38"** 65 Request Quote For This Product 
CW02602 14 3 0.03 0.045 .40" 92 Request Quote For This Product 
CW02603 14 4 0.03 0.045 .44" 118 Request Quote For This Product 
CW02604 14 5 0.03 0.045 .48" 140 Request Quote For This Product 
CW02605 14 7 0.03 0.045 .52" 180 Request Quote For This Product 
CW02606 14 9 0.03 0.06 .63" 250 Request Quote For This Product 
CW02607 14 10 0.03 0.06 .69" 275 Request Quote For This Product 
CW02608 14 12 0.03 0.06 .72" 310 Request Quote For This Product 
CW02609 14 15 0.03 0.06 .77" 380 Request Quote For This Product 
CW02610 14 19 0.03 0.06 .82" 460 Request Quote For This Product 
CW02611 14 20 0.03 0.08 .90" 520 Request Quote For This Product 
CW02612 14 25 0.03 0.08 1.00" 640 Request Quote For This Product 
CW02613 14 30 0.03 0.08 1.08" 740 Request Quote For This Product 
CW02614 14 37 0.03 0.08 1.14" 890 Request Quote For This Product 
Displaying 1 to 14 (of 14 products) Result Pages:  1 
* To specify ICEA Method 1 Table E-1 (Formerly K-1), add suffix "M1" to corresponding Charlotte Wire Part Number.
** Flat Construction.
Application
Suitable for control, signal, or lighting circuits rated 600Volts in power plants and heavy industrial locations where flame-resistance, stability in heat, physical durability, and excellent reliability is needed.
May be used as sunlight resistant, directly buried, and wet or dry locations.
Per NEC Articles 336 and 392, approved for installation in
1) raceways and cable tray systems including ladders, troughs, channels, solid bottom trays, and other similar structures,
2) lighting, control, and signal circuits,
3) aerial locations where supported by a messenger wire,
4) hazardous locations per NEC Article 501 Class 1 Division 2, and
5) Class 1 circuits as permitted in NEC Article 725-21(B).
Standards
UL 1277 for Type TC Cables.
Passes UL and IEEE383 70,000 BTU and ICEA 210,000BTU flame test.
UL Standard 44 for Rubber Insulated Wire & Cable(XHHW2).
ICEA S-95-658/NEMA WC70 for Nonshielded 0-2kv Cables. (Formerly ICEA S-68-516/WC8).
NEC Articles 336 & 392 for Tray Cable uses and constructions.