FREP/CPE TRAY CABLE - #10AWG
TYPE TC - SUNLIGHT RESISTANT,DIRECT BURIAL
XHHW-2 VW1 CONDUCTORS, CPE JACKET, 600VOLTS
| Construction: |
| CONDUCTOR: |
7 STRANDED TINNED COPPER.
|
| INSULATION: |
THERMOSETTING FLAME-RETARDANT ETHYLENE PROPYLENE RUBBER TYPE XHHW-2 VW1 PER UL 44. INSULATED CONDUCTORS RATED 90°C WET OR DRY.
|
| CONDUCTOR IDENTIFICATION: |
INSULATED CONDUCTORS ARE COLOR CODED PER ICEA METHOD 1 TABLE E-2 OF ICEA S-73-532 (FORMERLY K-2).*
|
| ASSEMBLY: |
CONDUCTORS ARE CABLED TOGETHER WITH A SUITABLE TAPE SEPARATOR AS NEEDED.
|
| OVERALL JACKET: |
SUNLIGHT RESISTANT, FLAME RETARDANT BLACK CPE PER UL 1277, WHICH PROTECTS AGAINST HEAT, FLAME, CHEMICALS, MOISTURE, AND MECHANICAL DAMAGE.
|
| Charlotte Wire Part#* ↓ |
Size AWG |
Number of Conductors |
Insulation Thickness (in.) |
Jacket Thickness (in.) |
Overall Diameter (in.) |
Approx. Net Wt. (Lbs/Mft) |
Add to Quote Cart |
| CW02640 |
10 |
2 |
0.03 |
0.045 |
.29" x .47"** |
115 |
|
| CW02641 |
10 |
3 |
0.03 |
0.045 |
.49" |
170 |
|
| CW02642 |
10 |
4 |
0.03 |
0.06 |
.57" |
235 |
|
| CW02643 |
10 |
5 |
0.03 |
0.06 |
.62" |
283 |
|
| CW02644 |
10 |
7 |
0.03 |
0.06 |
.67" |
378 |
|
| CW02645 |
10 |
9 |
0.03 |
0.06 |
.80" |
460 |
|
| CW02646 |
10 |
10 |
0.03 |
0.08 |
.90" |
570 |
|
| CW02647 |
10 |
12 |
0.03 |
0.08 |
.94" |
650 |
|
| CW02648 |
10 |
15 |
0.03 |
0.08 |
1.02" |
790 |
|
| CW02649 |
10 |
19 |
0.03 |
0.08 |
1.08" |
975 |
|
| CW02650 |
10 |
25 |
0.03 |
0.08 |
1.26" |
1240 |
|
| CW02651 |
10 |
37 |
0.03 |
0.08 |
1.44" |
1770 |
|
| Displaying 1 to 12 (of 12 products) |
Result Pages: 1 |
| * To specify ICEA Method 1 Table E-1(Formerly K-1), add suffix "M1" to corresponding Charlotte Wire Part Number.
|
| ** Flat Construction
|
| Application |
| Suitable for control, signal, or lighting circuits rated 600Volts in power plants and heavy industrial locations where flame-resistance, stability in heat, physical durability, and excellent reliability is needed.
|
| May be used as sunlight resistant, directly buried, and wet or dry locations.
|
| Per NEC Articles 336 and 392, approved for installation in
|
| 1) raceways and cable tray systems including ladders, troughs, channels, solid bottom trays, and other similar structures,
|
| 2) lighting, control, and signal circuits,
|
| 3) aerial locations where supported by a messenger wire,
|
| 4) hazardous locations per NEC Article 501 Class 1 Division 2, and
|
| 5) Class 1 circuits as permitted in NEC Article 725-21(B).
|
| Standards |
| UL 1277 for Type TC Cables.
|
| Passes UL and IEEE383 70,000 BTU and ICEA 210,000BTU flame test.
|
| UL Standard 44 for Rubber Insulated Wire & Cable(XHHW2).
|
| ICEA S-95-658/NEMA WC70 for Nonshielded 0-2kv Cables. (Formerly ICEA S-68-516/NEMA WC-8).
|
| NEC Articles 336 & 392 for Tray Cable uses and constructions.
|
|
|