FREP/CPE TRAY CABLE 3 CONDUCTOR W/GND
TYPE TC - SUNLIGHT RESISTANT,DIRECT BURIAL
XHHW-2 VW1 CONDUCTORS, CPE JACKET, 600VOLTS
Click  for Printer Friendly Spec Sheet. | Construction: |
| CONDUCTOR: |
CLASS B STRANDED TINNED COPPER.
|
| INSULATION: |
THERMOSETTING FLAME-RETARDANT ETHYLENE PROPYLENE RUBBER TYPE XHHW-2 VW1 PER UL 44. INSULATED CONDUCTORS RATED 90°C WET OR DRY.
|
| CONDUCTOR IDENTIFICATION: |
INSULATED CONDUCTORS COLOR CODED PER ICEA METHOD 4 (BLACK WITH PRINTED NUMBERS) ON #8 AND LARGER.
|
| SIZES #12 AND #10 COLOR CODED PER ICEA METHOD 1 TABLE E-2 OF ICEA S-73-532 (FORMERLY K-2). E-2 IS BLACK-RED-BLUE.
|
| ASSEMBLY: |
CONDUCTORS CABLED TOGETHER WITH A STRANDED COPPER GROUND WIRE IN ONE OF THE INTERSTICES, SUITABLE FILLERS FOR ROUNDNESS WHERE NEEDED, AND CABLE TAPE.
|
| OVERALL JACKET: |
SUNLIGHT RESISTANT, FLAME RETARDANT BLACK CPE PER UL 1277, WHICH PROTECTS AGAINST HEAT, FLAME, CHEMICALS, MOISTURE, AND MECHANICAL DAMAGE.
|
| Charlotte Wire Part# ↑ |
Size AWG |
Number of C'drs |
Number of Strands |
Insulation Thickness (in.) |
Jacket Thickness (in.) |
Gnd Wire AWG |
Overall Diameter (in.) |
Approx. Net Wt. (Lbs/Mft) |
Add to Quote Cart |
| CW02671 |
1000MCM |
3 |
61 |
0.08 |
0.14 |
1/0 |
3.20" |
11700 |
|
| CW02670 |
750MCM |
3 |
61 |
0.08 |
0.11 |
1 |
2.84" |
8990 |
|
| CW02669 |
500MCM |
3 |
37 |
0.065 |
0.11 |
2 |
2.28" |
6080 |
|
| CW02668 |
350MCM |
3 |
37 |
0.065 |
0.11 |
3 |
2.00" |
4320 |
|
| CW02667 |
250MCM |
3 |
37 |
0.065 |
0.11 |
4 |
1.76" |
3230 |
|
| CW02666 |
4/0 |
3 |
19 |
0.055 |
0.08 |
4 |
1.57" |
2650 |
|
| CW02665 |
3/0 |
3 |
19 |
0.055 |
0.08 |
4 |
1.45" |
2260 |
|
| CW02664 |
2/0 |
3 |
19 |
0.055 |
0.08 |
6 |
1.33" |
1770 |
|
| CW02663 |
1/0 |
3 |
19 |
0.055 |
0.08 |
6 |
1.23" |
1490 |
|
| CW02662 |
1 |
3 |
19 |
0.055 |
0.08 |
6 |
1.16" |
1275 |
|
| CW02661 |
2 |
3 |
7 |
0.045 |
0.08 |
6 |
1.02" |
1015 |
|
| CW02660 |
4 |
3 |
7 |
0.045 |
0.08 |
8 |
.88" |
686 |
|
| CW02659 |
6 |
3 |
7 |
0.045 |
0.06 |
8 |
.76" |
460 |
|
| CW02658 |
8 |
3 |
7 |
0.045 |
0.06 |
10 |
.68" |
332 |
|
| CW02657 |
10 |
3 |
7 |
0.03 |
0.045 |
10 |
.49" |
208 |
|
| CW02656 |
12 |
3 |
7 |
0.03 |
0.045 |
12 |
.43" |
149 |
|
| Displaying 1 to 16 (of 16 products) |
Result Pages: 1 |
| Application |
| Power circuits rated 600Volts in power plants and heavy industrial locations where flame resistance, stability in heat, physical durability, and excellent reliability is needed.
|
| May be used as sunlight resistant, directly buried, and wet or dry locations.
|
| Per NEC Articles 336 and 392, approved for installation in
|
| 1) raceways and cable tray systems including ladders, troughs, channels, solid bottom trays, and other similar structures,
|
| 2) aerial locations where supported by a messenger wire and
|
| 3) hazardous locations per NEC Art.501 Class 1 Division 2.
|
| Standards |
| UL 1277 for Type TC Cables.
|
| Passes UL and IEEE383 70,000BTU and ICEA 210,000BTU flame test.
|
| UL Standard 44 for Rubber Insulated Wire and Cable (XHHW-2).
|
| ICEA S-95-658/NEMA WC70 for Nonshielded 0-2kv Cables. (Formerly ICEA S-68-516/NEMA WC-8).
|
| NEC Articles 336 & 392 for Tray cable uses and constructions.
|
|