XLP/HYPALON® TRAY CABLE - #12AWG
TYPE TC - SUNLIGHT RESISTANT,DIRECT BURIAL
XHHW-2 VW1 CONDUCTORS, CSPE JACKET, 600VOLTS
Click  for Printer Friendly Spec Sheet. | Construction: |
| CONDUCTOR: |
7 STRANDED TINNED ANNEALED COPPER.
|
| INSULATION: |
FLAME-RETARDANT CROSSLINKED POLYETHYLENE (XLP) TYPE XHHW-2 V PER UL 44.
|
| INSULATED CONDUCTORS RATED 90°C WET OR DRY.
|
| CONDUCTOR IDENTIFICATION: |
INSULATED CONDUCTORS ARE COLOR CODED PER ICEA METHOD 1 TABLE E-2 OF ICEA S-73-532. (FORMERLY K-2).*
|
| ASSEMBLY: |
CONDUCTORS ARE CABLED TOGETHER WITH A SUITABLE TAPE SEPARATOR AS NEEDED.
|
| OVERALL JACKET: |
SUNLIGHT RESISTANT, FLAME RETARDANT BLACK HYPALON® (CHLOROSULFONATED POLYETHYLENE) PER UL 1277, WHICH PROTECTS AGAINST HEAT, FLAME, CHEMICALS, MOISTURE, AND MECHANICAL DAMAGE.
|
| Charlotte Wire Part#* ↓ |
Size AWG |
Number of Conductors |
Insulation Thickness (in.) |
Jacket Thickness (in.) |
Overall Diameter (in.) |
Approx. Net Wt. (Lbs/Mft) |
Add to Quote Cart |
| CW02718 |
12 |
2 |
0.03 |
0.045 |
.26 x .42"** |
89 |
|
| CW02719 |
12 |
3 |
0.03 |
0.045 |
.44" |
142 |
|
| CW02720 |
12 |
4 |
0.03 |
0.045 |
.48" |
179 |
|
| CW02721 |
12 |
5 |
0.03 |
0.045 |
.54" |
225 |
|
| CW02722 |
12 |
7 |
0.03 |
0.06 |
.61" |
280 |
|
| CW02723 |
12 |
9 |
0.03 |
0.06 |
.71" |
350 |
|
| CW02724 |
12 |
12 |
0.03 |
0.06 |
.80" |
445 |
|
| CW02725 |
12 |
15 |
0.03 |
0.08 |
.89" |
565 |
|
| CW02726 |
12 |
19 |
0.03 |
0.08 |
.96" |
730 |
|
| CW02727 |
12 |
25 |
0.03 |
0.08 |
1.12" |
920 |
|
| CW02728 |
12 |
30 |
0.03 |
0.08 |
1.20" |
1076 |
|
| CW02729 |
12 |
37 |
0.03 |
0.08 |
1.29" |
1325 |
|
| Displaying 1 to 12 (of 12 products) |
Result Pages: 1 |
| ® Hypalon® is a Dupont Trademark. (Also known as chlorosulfonated polyethylene or CSPE.)
|
| * To specify Method 1 Table E-1(formerly K-1), add suffix "M1" to Charlotte Wire Part Number.
|
| ** Flat Construction: Also available in round construction. (Specify round if desired.)
|
| Application |
| Suitable for control, signal, or lighting circuits rated 600Volts in power plants and heavy industrial locations where flame-resistance, stability in heat, physical durability, and excellent reliability is needed.
|
| May be used as sunlight resistant, directly buried, and wet or dry locations.
|
| Per NEC Articles 336 and 392, approved for installation in
|
| 1) raceways and cable tray systems including ladders, troughs, channels, solid bottom trays, and other similar structures,
|
| 2) lighting, control, and signal circuits,
|
| 3) aerial locations where supported by a messenger wire,
|
| 4) hazardous locations per NEC Article 501 Class 1 Division 2, and
|
| 5) Class 1 circuits as permitted in NEC Article 725-21(B).
|
| Standards |
| UL 1277 for Type TC Cables.
|
| Passes UL and IEEE383 70,000 BTU and ICEA 210,000BTU flame test.
|
| UL Standard 44 for XHHW-2 Conductors.
|
| ICEA S-95-658/NEMA WC70 for Nonshielded 0-2kv Cables. (Formerly ICEA S-66-524/NEMA WC-7).
|
| NEC Articles 336 & 392 for Tray Cable uses and constructions.
|
|