XLP/HYPALON® TRAY CABLE
3 CONDUCTOR WITH GROUND
TYPE TC - SUNLIGHT RESISTANT,DIRECT BURIAL
XHHW-2 VW1 CONDUCTORS, CSPE JACKET, 600VOLTS
Click  for Printer Friendly Spec Sheet. | Construction: |
| CONDUCTOR: |
CLASS B STRANDED TINNED COPPER.
|
| INSULATION: |
FLAME-RETARDANT CROSSLINKED POLYETHYLENE (XLP) TYPE XHHW-2 VW1 PER UL 44. INSULATED CONDUCTORS RATED 90°C WET OR DRY.
|
| CONDUCTOR IDENTIFICATION: |
INSULATED CONDUCTORS COLOR CODED PER ICEA METHOD 4 (BLACK WITH PRINTED NUMBERS) ON #8 AND LARGER. SIZES #12 AND #10 COLOR CODED PER ICEA METHOD 1 TABLE E-2 (BLACK-RED-BLUE).
|
| ASSEMBLY: |
CONDUCTORS CABLED TOGETHER WITH A STRANDED COPPER GROUND WIRE IN ONE OF THE INTERSTICES, SUITABLE FILLERS FOR ROUNDNESS WHERE NEEDED, AND CABLE TAPE.
|
| OVERALL JACKET: |
SUNLIGHT RESISTANT, FLAME RETARDANT BLACK HYPALON® (CHLOROSULFONATED POLYETHYLENE) PER UL 1277, WHICH PROTECTS AGAINST HEAT, FLAME, CHEMICALS, MOISTURE, AND MECHANICAL DAMAGE.
|
| Charlotte Wire Part# ↑ |
Size AWG |
Number of C'dfs |
Number of Strands |
Insulation Thickness (in.) |
Jacket Thickness (in.) |
Gnd Wire AWG |
Overall Diameter (in.) |
Approx. Net Wt. (Lbs/Mft) |
Add to Quote Cart |
| CW02775 |
750MCM |
3 |
61 |
0.08 |
0.11 |
1 |
2.84" |
9050 |
|
| CW02774 |
500MCM |
3 |
37 |
0.065 |
0.11 |
2 |
2.28" |
6210 |
|
| CW02773 |
350MCM |
3 |
37 |
0.065 |
0.11 |
3 |
2.00" |
4550 |
|
| CW02772 |
250MCM |
3 |
37 |
0.065 |
0.11 |
4 |
1.76" |
3340 |
|
| CW02771 |
4/0 |
3 |
19 |
0.055 |
0.08 |
4 |
1.57" |
2740 |
|
| CW02770 |
3/0 |
3 |
19 |
0.055 |
0.08 |
4 |
1.45" |
2290 |
|
| CW02769 |
2/0 |
3 |
19 |
0.055 |
0.08 |
6 |
1.33" |
1860 |
|
| CW02768 |
1/0 |
3 |
19 |
0.055 |
0.08 |
6 |
1.23" |
1520 |
|
| CW02767 |
1 |
3 |
19 |
0.055 |
0.08 |
6 |
1.16" |
1275 |
|
| CW02766 |
2 |
3 |
7 |
0.045 |
0.08 |
6 |
1.02" |
1030 |
|
| CW02765 |
4 |
3 |
7 |
0.045 |
0.08 |
8 |
.88" |
700 |
|
| CW02764 |
6 |
3 |
7 |
0.045 |
0.06 |
8 |
.76" |
475 |
|
| CW02763 |
8 |
3 |
7 |
0.045 |
0.06 |
10 |
.68" |
348 |
|
| CW02762 |
10 |
3 |
7 |
0.03 |
0.045 |
10 |
.49" |
225 |
|
| CW02761 |
12 |
3 |
7 |
0.03 |
0.045 |
12 |
.43" |
155 |
|
| Displaying 1 to 15 (of 15 products) |
Result Pages: 1 |
| ® Hypalon® is a Dupont Trademark. (Also known as chlorosulfonated polyethylene or CSPE.)
|
| Application |
| Power circuits rated 600Volts in power plants and heavy industrial locations where flame resistance, stability in heat, physical durability, and excellent reliability is needed.
|
| May be used as sunlight resistant, directly buried, and wet or dry locations.
|
| Per NEC Articles 336 and 392, approved for installation in
|
| 1) raceways and cable tray systems including ladders, troughs, channels, solid bottom trays, and other similar structures,
|
| 2) aerial locations where supported by a messenger wire and
|
| 3) hazardous locations per NEC Art.501 Class 1 Division 2.
|
| Standards |
| UL 1277 for Type TC Cables.
|
| Passes UL and IEEE383 70,000BTU and ICEA 210,000BTU flame test.
|
| UL Standard 44 for XHHW-2 Conductors.
|
| ICEA S-95-658/NEMA WC70 for Nonshielded 0-2kv Cables. (Formerly ICEA S-66-524/NEMA WC-7).
|
| NEC Articles 336 and 392 for Tray Cable uses and constructions.
|
| Optional Constructions |
| EPR Insulation.
|
|