XLP/HYPALON® TRAY CABLE
3 CONDUCTOR WITH GROUND
TYPE TC - SUNLIGHT RESISTANT,DIRECT BURIAL
XHHW-2 VW1 CONDUCTORS, CSPE JACKET, 600VOLTS

Construction:
CONDUCTOR: CLASS B STRANDED TINNED COPPER.
INSULATION: FLAME-RETARDANT CROSSLINKED POLYETHYLENE (XLP) TYPE XHHW-2 VW1 PER UL 44. INSULATED CONDUCTORS RATED 90°C WET OR DRY.
CONDUCTOR IDENTIFICATION: INSULATED CONDUCTORS COLOR CODED PER ICEA METHOD 4 (BLACK WITH PRINTED NUMBERS) ON #8 AND LARGER. SIZES #12 AND #10 COLOR CODED PER ICEA METHOD 1 TABLE E-2 (BLACK-RED-BLUE).
ASSEMBLY: CONDUCTORS CABLED TOGETHER WITH A STRANDED COPPER GROUND WIRE IN ONE OF THE INTERSTICES, SUITABLE FILLERS FOR ROUNDNESS WHERE NEEDED, AND CABLE TAPE.
OVERALL JACKET: SUNLIGHT RESISTANT, FLAME RETARDANT BLACK HYPALON® (CHLOROSULFONATED POLYETHYLENE) PER UL 1277, WHICH PROTECTS AGAINST HEAT, FLAME, CHEMICALS, MOISTURE, AND MECHANICAL DAMAGE.
 Charlotte Wire Part# ↓   Size AWG   Number of C'dfs   Number of Strands   Insulation Thickness (in.)   Jacket Thickness (in.)   Gnd Wire AWG   Overall Diameter (in.)   Approx. Net Wt. (Lbs/Mft)   Add to Quote Cart 
CW02761 12 3 7 0.03 0.045 12 .43" 155 Request Quote For This Product 
CW02762 10 3 7 0.03 0.045 10 .49" 225 Request Quote For This Product 
CW02763 8 3 7 0.045 0.06 10 .68" 348 Request Quote For This Product 
CW02764 6 3 7 0.045 0.06 8 .76" 475 Request Quote For This Product 
CW02765 4 3 7 0.045 0.08 8 .88" 700 Request Quote For This Product 
CW02766 2 3 7 0.045 0.08 6 1.02" 1030 Request Quote For This Product 
CW02767 1 3 19 0.055 0.08 6 1.16" 1275 Request Quote For This Product 
CW02768 1/0 3 19 0.055 0.08 6 1.23" 1520 Request Quote For This Product 
CW02769 2/0 3 19 0.055 0.08 6 1.33" 1860 Request Quote For This Product 
CW02770 3/0 3 19 0.055 0.08 4 1.45" 2290 Request Quote For This Product 
CW02771 4/0 3 19 0.055 0.08 4 1.57" 2740 Request Quote For This Product 
CW02772 250MCM 3 37 0.065 0.11 4 1.76" 3340 Request Quote For This Product 
CW02773 350MCM 3 37 0.065 0.11 3 2.00" 4550 Request Quote For This Product 
CW02774 500MCM 3 37 0.065 0.11 2 2.28" 6210 Request Quote For This Product 
CW02775 750MCM 3 61 0.08 0.11 1 2.84" 9050 Request Quote For This Product 
Displaying 1 to 15 (of 15 products) Result Pages:  1 
® Hypalon® is a Dupont Trademark. (Also known as chlorosulfonated polyethylene or CSPE.)
Application
Power circuits rated 600Volts in power plants and heavy industrial locations where flame resistance, stability in heat, physical durability, and excellent reliability is needed.
May be used as sunlight resistant, directly buried, and wet or dry locations.
Per NEC Articles 336 and 392, approved for installation in
1) raceways and cable tray systems including ladders, troughs, channels, solid bottom trays, and other similar structures,
2) aerial locations where supported by a messenger wire and
3) hazardous locations per NEC Art.501 Class 1 Division 2.
Standards
UL 1277 for Type TC Cables.
Passes UL and IEEE383 70,000BTU and ICEA 210,000BTU flame test.
UL Standard 44 for XHHW-2 Conductors.
ICEA S-95-658/NEMA WC70 for Nonshielded 0-2kv Cables. (Formerly ICEA S-66-524/NEMA WC-7).
NEC Articles 336 and 392 for Tray Cable uses and constructions.
Optional Constructions
EPR Insulation.