XLP/CPE TRAY CABLE - 10AWG
TYPE TC - SUNLIGHT RESISTANT,DIRECT BURIAL
XHHW-2 CONDUCTORS, CPE JACKET, 600VOLTS

Construction:
CONDUCTOR: 7 STRANDED COPPER TO ASTM B-3.
INSULATION: THERMOSETTING XLP TYPE XHHW-2 PER UL 44. INSULATED CONDUCTORS RATED 90°C WET OR DRY.
CONDUCTOR IDENTIFICATION: INSULATED CONDUCTORS ARE COLOR CODED PER ICEA METHOD 1 TABLE E-2 OF ICEA S-73-532. (FORMERLY K-2).*
ASSEMBLY: CONDUCTORS ARE CABLED TOGETHER WITH A SUITABLE TAPE SEPARATOR AS NEEDED.
OVERALL JACKET: SUNLIGHT RESISTANT, FLAME RETARDANT BLACK CPE PER UL 1277, WHICH PROTECTS AGAINST HEAT, FLAME, CHEMICALS, MOISTURE, AND MECHANICAL DAMAGE.
 Charlotte Wire Part#* ↓   Size AWG   Number of Conductors   Insulation Thickness (in.)   Jacket Thickness (in.)   Overall Diameter (in.)   Approx. Net Wt. (Lbs/Mft)   Add to Quote Cart 
CW02841 10 2 0.03 0.045 .29" x .47"** 115 Request Quote For This Product 
CW02842 10 3 0.03 0.045 .49" 170 Request Quote For This Product 
CW02843 10 4 0.03 0.06 .57" 235 Request Quote For This Product 
CW02844 10 5 0.03 0.06 .62" 283 Request Quote For This Product 
CW02845 10 7 0.03 0.06 .67" 378 Request Quote For This Product 
CW02846 10 9 0.03 0.06 .80" 460 Request Quote For This Product 
CW02847 10 10 0.03 0.08 .90" 570 Request Quote For This Product 
CW02848 10 12 0.03 0.08 .94" 650 Request Quote For This Product 
CW02849 10 15 0.03 0.08 1.02" 790 Request Quote For This Product 
CW02850 10 19 0.03 0.08 1.08" 975 Request Quote For This Product 
CW02851 10 25 0.03 0.08 1.26" 1240 Request Quote For This Product 
CW02852 10 37 0.03 0.08 1.44" 1770 Request Quote For This Product 
Displaying 1 to 12 (of 12 products) Result Pages:  1 
* To specify Method 1 Table E-1(formerly K-1), add suffix "M1" to Charlotte Wire Part Number.
** Flat Construction
Application
Suitable for control, signal, or lighting circuits rated 600Volts in power plants and heavy industrial locations where flame-resistance, stability in heat, physical durability, and excellent reliability is needed.
May be used as sunlight resistant, directly buried, and wet or dry locations.
Per NEC Articles 336 and 392, approved for installation in
1) raceways and cable tray systems including ladders, troughs, channels, solid bottom trays, and other similar structures,
2) lighting, control, and signal circuits,
3) aerial locations where supported by a messenger wire,
4) hazardous locations per NEC Article 501 Class 1 Division 2, and
5) Class 1 circuits as permitted in NEC Article 725-21(b).
Standards
UL 1277 for Type TC Cables.
Passes UL and IEEE383 70,000 BTU and ICEA 210,000BTU flame test.
UL Standard 44 for XHHW-2 Conductors.
ICEA S-95-658/NEMA WC70 for Nonshielded 0 - 2KV Cables. (Formerly ICEA S-66-524/NEMA WC70).
NEC Articles 336 & 392 for Tray Cable Uses and Constructions.