PENDANT AND REELING CONTROL CABLE
TYPE TC #14AWG - SMALL DIAMETER
90°C, 600VOLTS, UL 1277 SUNLIGHT RESISTANT
| Construction: |
| CONDUCTOR: |
19 STRANDED SOFT DRAWN BARE COPPER.
|
| INSULATION: |
FLAME-RETARDANT POLYMER WITH NYLON JACKET.
|
| CONDUCTOR IDENTIFICATION: |
INSULATED CONDUCTORS ARE COLOR CODED PER ICEA METHOD 1 TABLE E-2 OF ICEA S-73-532. (FORMERLY K-2)
|
| ASSEMBLY: |
CONDUCTORS ARE CABLED TOGETHER WITH SUITABLE FILLERS WHERE NEEDED AND A MYLAR TAPE SEPARATOR IS APPLIED OVER THE CONDUCTOR ASSEMBLY.
|
| OVERALL JACKET: |
HEAVY DUTY THERMOSETTING BLACK NEOPRENE PER UL 1277, WHICH PROTECTS AGAINST FLAME, CHEMICALS, OIL, MOISTURE, SUNLIGHT, AND ABRASION.
|
| Charlotte Wire Part# ↓ |
Size AWG |
Number of Conductors |
Insulation Thickness (in.) Polymer |
Insulation Thickness (in.) Nylon |
Jacket Thickness (in.) |
Overall Diameter (in.) |
Approx. Net Wt. (Lbs/Mft) |
Add to Quote Cart |
| CW03295 |
14 |
3 |
0.015 |
0.004 |
0.045 |
.32" |
90 |
|
| CW03296 |
14 |
4 |
0.015 |
0.004 |
0.045 |
.38" |
110 |
|
| CW03297 |
14 |
5 |
0.015 |
0.004 |
0.045 |
.42" |
150 |
|
| CW03298 |
14 |
6 |
0.015 |
0.004 |
0.045 |
.45" |
150 |
|
| CW03299 |
14 |
7 |
0.015 |
0.004 |
0.045 |
.45" |
165 |
|
| CW03300 |
14 |
8 |
0.015 |
0.004 |
0.045 |
.52" |
200 |
|
| CW03301 |
14 |
9 |
0.015 |
0.004 |
0.06 |
.57" |
235 |
|
| CW03302 |
14 |
10 |
0.015 |
0.004 |
0.06 |
.60" |
255 |
|
| CW03303 |
14 |
12 |
0.015 |
0.004 |
0.06 |
.61" |
290 |
|
| CW03304 |
14 |
16 |
0.015 |
0.004 |
0.06 |
.68" |
360 |
|
| CW03305 |
14 |
19 |
0.015 |
0.004 |
0.06 |
.71" |
430 |
|
| CW03306 |
14 |
20 |
0.015 |
0.004 |
0.06 |
.78" |
450 |
|
| CW03307 |
14 |
21 |
0.015 |
0.004 |
0.06 |
.79" |
470 |
|
| CW03308 |
14 |
24 |
0.015 |
0.004 |
0.06 |
.83" |
515 |
|
| CW03309 |
14 |
30 |
0.015 |
0.004 |
0.08 |
.91" |
660 |
|
| CW03310 |
14 |
37 |
0.015 |
0.004 |
0.08 |
.99" |
785 |
|
| Displaying 1 to 16 (of 16 products) |
Result Pages: 1 |
| Application |
| Designed for use in flexing and reeling applications where mechanical toughness and small diameters are needed, such as cranes, hoists, pendant stations, platforms, and other moving industrial equipment.
|
| May be used in indoor and outdoor applications, including sunlight resistant, direct burial, and wet or dry locations.
|
| Per NEC Articles 336 and 392, approved for installation in
|
| 1) raceways and cable tray systems including ladders, troughs, channels, solid bottom trays, and other similar structures,
|
| 2) hazardous locations per Article 501 Class 1 Division 2, and
|
| 3) Class 1 circuits as permitted in Article 725-21(B).
|
| Standards |
| UL Standard 1277 for Type TC Cables.
|
| Passes UL and IEEE383 70,000 BTU Flame Test.
|
| NEC Articles 336 and 392 for Tray Cable uses and constructions.
|
|
|