PENDANT AND REELING CONTROL CABLE
TYPE TC #12AWG - SMALL DIAMETER
90°C, 600VOLTS, UL 1277 SUNLIGHT RESISTANT
| Construction: |
| CONDUCTOR: |
19 STRANDED SOFT DRAWN BARE COPPER.
|
| INSULATION: |
FLAME-RETARDANT POLYMER WITH NYLON JACKET.
|
| CONDUCTOR IDENTIFICATION: |
INSULATED CONDUCTORS ARE COLOR CODED PER ICEA METHOD 1 TABLE E-2 OF ICEA S-73-532. (FORMERLY K-2).
|
| ASSEMBLY: |
CONDUCTORS ARE CABLED TOGETHER WITH SUITABLE FILLERS WHERE NEEDED AND A MYLAR TAPE SEPARATOR IS APPLIED OVER THE CONDUCTOR ASSEMBLY.
|
| OVERALL JACKET: |
HEAVY DUTY THERMOSETTING BLACK NEOPRENE PER UL 1277, WHICH PROTECTS AGAINST FLAME, CHEMICALS, OIL, MOISTURE, SUNLIGHT, AND ABRASION.
|
| Charlotte Wire Part# ↑ |
Size AWG |
Number of Conductors |
Insulation Thickness (in.) Polymer |
Insulation Thickness (in.) Nylon |
Jacket Thickness (in.) |
Overall Diameter (in.) |
Approx. Net Wt. (Lbs/Mft) |
Add to Quote Cart |
| CW03333 |
12 |
37 |
0.015 |
0.004 |
0.08 |
1.10" |
1020 |
|
| CW03332 |
12 |
30 |
0.015 |
0.004 |
0.08 |
1.04" |
930 |
|
| CW03331 |
12 |
24 |
0.015 |
0.004 |
0.08 |
.98" |
775 |
|
| CW03330 |
12 |
21 |
0.015 |
0.004 |
0.08 |
.89" |
680 |
|
| CW03329 |
12 |
20 |
0.015 |
0.004 |
0.08 |
.87" |
655 |
|
| CW03328 |
12 |
19 |
0.015 |
0.004 |
0.06 |
.80" |
605 |
|
| CW03327 |
12 |
16 |
0.015 |
0.004 |
0.06 |
.75" |
505 |
|
| CW03326 |
12 |
12 |
0.015 |
0.004 |
0.06 |
.68" |
395 |
|
| CW03325 |
12 |
10 |
0.015 |
0.004 |
0.06 |
.67" |
350 |
|
| CW03324 |
12 |
8 |
0.015 |
0.004 |
0.045 |
.61" |
300 |
|
| CW03323 |
12 |
6 |
0.015 |
0.004 |
0.045 |
.50" |
210 |
|
| CW03322 |
12 |
5 |
0.015 |
0.004 |
0.045 |
.46" |
185 |
|
| CW03321 |
12 |
4 |
0.015 |
0.004 |
0.045 |
.42" |
155 |
|
| CW03320 |
12 |
3 |
0.015 |
0.004 |
0.045 |
.39" |
120 |
|
| Displaying 1 to 14 (of 14 products) |
Result Pages: 1 |
| Application |
| Designed for use in flexing and reeling applications where mechanical toughness and small diameters are needed, such as cranes, hoists, pendant stations, platforms, and other moving industrial equipment.
|
| May be used in indoor and outdoor applications, including sunlight resistant, direct burial, and wet or dry locations.
|
| Per NEC Articles 336 and 392, approved for installation in
|
| 1) raceways and cable tray systems including ladders, troughs, channels, solid bottom trays, and other similar structures,
|
| 2) hazardous locations per Article 501 Class 1 Division 2, and
|
| 3) Class 1 circuits as permitted in Article 725-21(B).
|
| Standards |
| UL Standard 1277 for Type TC Cables.
|
| Passes UL and IEEE383 70,000 BTU Flame Test.
|
| NEC Articles 336 and 392 for Tray Cable uses and constructions.
|
|
|