SWITCHBOARD WIRE
90°C XLP INSULATION - TINNED COPPER
UL TYPE SIS, 600VOLTS
| Construction: |
| CONDUCTOR: |
SOFT DRAWN STRANDED TINNED COPPER. |
| INSULATION: |
THERMOSETTING CROSSLINKED POLYETHYLENE(XLP). |
| Charlotte Wire Part# ↓ |
Size AWG |
Number of Strands |
Strand Size |
Insulation Thickness (in.) |
Overall Diameter (in.) |
Approx. Net Weight (Lbs/Mft) |
Add to Quote Cart |
| CW04001 |
18* |
16 |
30AWG |
0.03 |
.12" |
11 |
|
| CW04002 |
16* |
26 |
30AWG |
0.03 |
.13" |
14 |
|
| CW04003 |
14 |
7 |
.0242" |
0.03 |
.14" |
20 |
|
| CW04004 |
14 |
41 |
30AWG |
0.03 |
.14" |
20 |
|
| CW04005 |
12 |
7 |
.0305" |
0.03 |
.16" |
30 |
|
| CW04006 |
12 |
65 |
30AWG |
0.03 |
.16" |
30 |
|
| CW04007 |
10 |
7 |
.0385" |
0.03 |
.18" |
41 |
|
| CW04008 |
10 |
105 |
30AWG |
0.03 |
.19" |
42 |
|
| CW04009 |
8 |
7 |
.0486" |
0.045 |
.24" |
67 |
|
| CW04010 |
8 |
133 |
29AWG |
0.045 |
.26" |
70 |
|
| CW04011 |
6 |
7 |
.0612" |
0.06 |
.32" |
105 |
|
| CW04012 |
6 |
133 |
27AWG |
0.06 |
.34" |
110 |
|
| CW04013 |
4 |
7 |
.0772" |
0.06 |
.36" |
170 |
|
| CW04014 |
4 |
133 |
25AWG |
0.06 |
.39" |
180 |
|
| CW04015 |
2 |
7 |
.0974" |
0.06 |
.43" |
260 |
|
| CW04016 |
2 |
133 |
.0223" |
0.06 |
.46" |
268 |
|
| CW04017 |
1 |
19 |
.0591" |
0.08 |
.50" |
320 |
|
| CW04018 |
1/0 |
19 |
.0745" |
0.08 |
.55" |
405 |
|
| CW04019 |
2/0 |
19 |
.0837" |
0.08 |
.59" |
488 |
|
| CW04020 |
3/0 |
19 |
.0940" |
0.08 |
.65" |
595 |
|
| CW04021 |
4/0 |
19 |
.1055" |
0.08 |
.69" |
770 |
|
| Displaying 1 to 21 (of 21 products) |
Result Pages: 1 |
| * Sizes 18 and 16 AWG are not UL Type SIS. Minimum UL size for SIS is 14AWG. |
| Application |
| Suitable for the wiring of switchboards, panelboards, and distribution boards installed for the control of light and power circuits per NEC Article 408. |
| Standards |
| UL Type SIS: 90°C 600Volts. Sizes 14 through 4/0AWG) |
| Optional Constructions |
| Sizes 18AWG through 10AWG may be dual rated as UL 3173 and CSA CL1251. |
|
|