FEP INSULATED BUILDING WIRE
200°C, 600VOLTS
NEC TYPE FEP
Click  for Printer Friendly Spec Sheet. | Construction: |
| CONDUCTOR: |
STRANDED OR SOLID BARE COPPER
|
| INSULATION: |
FLUORINATED ETHYLENE PROPYLENE (FEP) TEFLON.®
|
| Charlotte Wire Part# ↓ |
Size AWG |
Number of Strands |
Insulation Thickness (in.) |
Ampacity 3/c* |
Ampacity 1/C** |
Overall Diameter (in.) |
Approx. Net Wt. (Lbs/Mft) |
Add to Quote Cart |
| CW04506SOLULFEP |
14 |
1 |
.020" |
36 |
54 |
.11" |
19 |
|
| CW04506ULFEP |
14 |
7 |
.020" |
36 |
54 |
.11" |
19 |
|
| CW04507SOLULFEP |
12 |
1 |
.020" |
45 |
68 |
.13" |
25 |
|
| CW04507ULFEP |
12 |
7 |
.020" |
45 |
68 |
.14" |
26 |
|
| CW04508ULFEP |
10 |
7 |
.020" |
60 |
90 |
.15" |
39 |
|
| CW04509ULFEP |
8 |
7 |
.030" |
83 |
124 |
.21" |
70 |
|
| CW04510ULFEP |
6 |
7 |
.030" |
110 |
165 |
.29" |
110 |
|
| CW04511ULFEP |
4 |
7 |
.030" |
125 |
220 |
.35" |
204 |
|
| CW04512ULFEP |
2 |
7 |
.030" |
171 |
293 |
.40" |
258 |
|
| Displaying 1 to 9 (of 9 products) |
Result Pages: 1 |
| ® Teflon® is a trademark of Dupont.
|
| * Ampacity based on 200°C Conductor and 40°C Ambient temperature with not more than 3 current carrying conductors per 2002 NEC Table 310-18.
|
| ** Ampacity based on 200°C Conductor and 40°C Ambient temperature with single conductor in free air per 2002 NEC Table 310-19.
|
| Application |
| For use as a signal, control, or power wire in demanding industrial locations.
|
| The FEP provides versatile properties such as wide temperature range (-70°C to 200°C), exceptional heat and flame resistance, excellent chemical resistance (including oil and gasoline), excellent sun, weather, and water resistance, abrasion resistance, and excellent electrical capabilities.
|
| Standards |
| NEC Type FEP
|
| 90°C Dry & Damp Locations.
|
| 200°C Dry Locations - where design conditions require maximum conductor operating temperatures above 90°C.
|
|