INSTRUMENT CABLE - NONSHIELDED
SINGLE PAIR OR TRIAD - TINNED COPPER
TYPE PLTC, 105°C, 300VOLTS

Construction:
CONDUCTOR: STRANDED TINNED COPPER.
INSULATION: FLAME RETARDANT PVC (COLOR CODE FOR PAIR IS BLACK - RED; COLOR CODE FOR TRIAD IS BLACK - RED - WHITE).
ASSEMBLY: INSULATED CONDUCTORS TWISTED TOGETHER INTO A PAIR (2/C) OR TRIAD (3/C) WITH AN APPROXIMATE 2" LAY OF TWIST.
JACKET: SUNLIGHT AND MOISTURE RESISTANT, FLAME RETARDANT GRAY PVC.
 Charlotte Wire Part# ↓   Number of Conductors   Size AWG   Number of Strands   Insulation Thickness (in.)   Jacket Thickness (in.)   Overall Diameter (in.)   Approx. Net Wt. (Lbs/Mft)   Add to Quote Cart 
CW05010 2 22 7 0.015 0.035 .19" 17 Request Quote For This Product 
CW05011 3 22 7 0.015 0.035 .21" 24 Request Quote For This Product 
CW05012 2 20 7 0.015 0.035 .21" 22 Request Quote For This Product 
CW05013 3 20 7 0.015 0.035 .22" 28 Request Quote For This Product 
CW05014 2 18 16 0.015 0.035 .23" 27 Request Quote For This Product 
CW05015 3 18 16 0.015 0.035 .24" 36 Request Quote For This Product 
CW05016 2 16 19 0.015 0.035 .25" 36 Request Quote For This Product 
CW05017 3 16 19 0.015 0.035 .26" 48 Request Quote For This Product 
CW05018 2 14 19 0.015 0.042 .28" 52 Request Quote For This Product 
CW05019 3 14 19 0.015 0.042 .34" 83 Request Quote For This Product 
CW05020 2 12 19 0.015 0.042 .34" 85 Request Quote For This Product 
Displaying 1 to 11 (of 11 products) Result Pages:  1 
Application
Instrumentation and Control Circuits rated 300volts or less.
Per NEC Article 725, approved for installation in
1) Cable trays indoors and outdoors,
2) raceways,
3) supported by a messenger wire,
4) hazardous locations per NEC Art.501-4(b) Class 1 Division 2,
5) Cable trays in hazardous locations per NEC Art.502-4(b) Class 2 Division 2, and
6) CL2 and CL3 applications.
Standards
UL Subject 13.
Passes UL and IEEE383 70,000BTU Flame Test.
NEC Article 725 Class 2 and Class 3 Circuits.