INSTRUMENT CABLE - OVERALL SHIELDED
NONSHIELDED PAIRS OR TRIADS - #20AWG
TYPE PLTC, 105°C, 300VOLTS
Click  for Printer Friendly Spec Sheet. | Construction: |
| CONDUCTOR: |
7 STRANDED BARE COPPER. |
| INSULATION: |
FLAME RETARDANT PVC. |
| COLOR CODE: |
PAIRS ARE CODED BLACK AND WHITE; TRIADS ARE CODED BLACK, |
| WHITE, AND RED. |
| ONE CONDUCTOR IN EACH PAIR OR TRIAD IS ALSO NUMBERED FOR EASE OF IDENTIFICATION. |
| ASSEMBLY: |
INSULATED CONDUCTORS ARE TWISTED INTO PAIRS OR TRIADS WITH AN APPROXIMATE 2" STAGGERED LAY OF TWIST TO REDUCE CROSSTALK. |
| TWISTED PAIRS CABLED WITH OVERALL ALUMINUM/MYLAR TAPE SHIELD AND STRANDED TINNED COPPER DRAIN WIRE TO PROVIDE 100% SHIELDING COVERAGE. |
| RIP CORD |
NYLON RIPCORD APPLIED UNDER JACKET TO HELP STRIP JACKET. |
| JACKET: |
SUNLIGHT AND MOISTURE RESISTANT, FLAME RETARDANT BLACK PVC. |
| Charlotte Wire Part# ↓ |
Size AWG |
Number of Pairs |
Number of Triads |
Insulation Thickness (in.) |
Jacket Thickness (in.) |
Overall Diameter (in.) |
Approx. Net Wt. (Lbs/Mft) |
Add to Quote Cart |
| CW05051 |
20 |
2 |
- |
0.015 |
0.04 |
.33" |
57 |
|
| CW05052 |
20 |
4 |
- |
0.015 |
0.04 |
.39" |
84 |
|
| CW05053 |
20 |
8 |
- |
0.015 |
0.05 |
.49" |
135 |
|
| CW05054 |
20 |
12 |
- |
0.015 |
0.05 |
.58" |
185 |
|
| CW05055 |
20 |
16 |
- |
0.015 |
0.06 |
.65" |
243 |
|
| CW05056 |
20 |
24 |
- |
0.015 |
0.06 |
.78" |
340 |
|
| CW05057 |
20 |
36 |
- |
0.015 |
0.07 |
.96" |
495 |
|
| CW05058 |
20 |
50 |
- |
0.015 |
0.07 |
1.10" |
659 |
|
| CW05059 |
20 |
- |
2 |
0.015 |
0.04 |
.37" |
72 |
|
| CW05060 |
20 |
- |
4 |
0.015 |
0.05 |
.45" |
111 |
|
| CW05061 |
20 |
- |
8 |
0.015 |
0.05 |
.56" |
187 |
|
| CW05062 |
20 |
- |
12 |
0.015 |
0.06 |
.70" |
280 |
|
| CW05063 |
20 |
- |
16 |
0.015 |
0.06 |
.82" |
344 |
|
| CW05064 |
20 |
- |
24 |
0.015 |
0.07 |
1.08" |
512 |
|
| Displaying 1 to 14 (of 14 products) |
Result Pages: 1 |
| Application |
| Instrumentation and Control Circuits rated 300volts or less. |
| Per NEC Article 725, approved for installation in |
| 1) Cable trays indoors and outdoors, |
| 2) raceways, |
| 3) supported by a messenger wire, |
| 4) hazardous locations per NEC Art.501-4(b) Class 1 Division 2, |
| 5) Cable trays in hazardous locations per NEC Art.502-4(b) Class 2 Division 2, and |
| 6) CL2 and CL3 applications. |
| Standards |
| UL Subject 13. |
| Passes UL and IEEE383 70,000BTU Flame Test. |
| NEC Article 725 Class 2 and Class 3 Circuits. |
|