INSTRUMENT CABLE - TINNED COPPER
INDIVIDUALLY SHIELDED PAIRS
TYPE PLTC, 105°C, 300VOLTS
Click  for Printer Friendly Spec Sheet. | Construction: |
| CONDUCTOR: |
STRANDED TINNED COPPER |
| INSULATION: |
FLAME RETARDANT PVC. |
| COLOR CODE: |
PAIRS ARE CODED BLACK AND RED. |
| ONE CONDUCTOR IN EACH PAIR IS ALSO NUMBERED FOR EASE OF IDENTIFICATION. |
| ASSEMBLY: |
INSULATED CONDUCTORS ARE TWISTED INTO PAIRS; TWISTED PAIRS INDIVIDUALLY SHIELDED WITH ALUMINUM/MYLAR TAPE SHIELD AND STRANDED TINNED COPPER DRAIN WIRE TO PROVIDE 100% SHIELDING COVERAGE. |
| SHIELDED PAIRS CABLED TOGETHER. |
| JACKET: |
SUNLIGHT AND MOISTURE RESISTANT, FLAME RETARDANT GRAY PVC. |
| Charlotte Wire Part# ↑ |
Size AWG |
Number of Pairs |
Number of Conductor Strands |
Insulation Thickness (in.) |
Jacket Thickness (in.) |
Overall Diameter (in.) |
Approx. Net Wt. (Lbs/Mft) |
Add to Quote Cart |
| CW05115 |
18 |
15 |
16 |
0.015 |
0.063 |
.81" |
409 |
|
| CW05114 |
18 |
11 |
16 |
0.015 |
0.063 |
.73" |
312 |
|
| CW05113 |
18 |
9 |
16 |
0.015 |
0.063 |
.65" |
239 |
|
| CW05112 |
18 |
6 |
16 |
0.015 |
0.053 |
.56" |
181 |
|
| CW05111 |
18 |
4 |
16 |
0.015 |
0.053 |
.49" |
126 |
|
| CW05110 |
18 |
3 |
16 |
0.015 |
0.053 |
.43" |
102 |
|
| CW05109 |
18 |
2 |
16 |
0.015 |
0.042 |
.38" |
71 |
|
| CW05108 |
22 |
51 |
7 |
0.015 |
0.075 |
1.05" |
520 |
|
| CW05107 |
22 |
19 |
7 |
0.015 |
0.063 |
.69" |
270 |
|
| CW05106 |
22 |
11 |
7 |
0.015 |
0.053 |
.56" |
165 |
|
| CW05105 |
22 |
9 |
7 |
0.015 |
0.053 |
.52" |
143 |
|
| CW05104 |
22 |
6 |
7 |
0.015 |
0.053 |
.46" |
101 |
|
| CW05103 |
22 |
4 |
7 |
0.015 |
0.042 |
.37" |
66 |
|
| CW05102 |
22 |
3 |
7 |
0.015 |
0.042 |
.34" |
54 |
|
| CW05101 |
22 |
2 |
7 |
0.015 |
0.042 |
.32" |
42 |
|
| Displaying 1 to 15 (of 15 products) |
Result Pages: 1 |
| Application |
| Instrumentation and Control Circuits rated 300volts or less. |
| Per NEC Article 725, approved for installation in |
| 1) Cable trays indoors and outdoors, |
| 2) raceways, |
| 3) supported by a messenger wire, |
| 4) hazardous locations per NEC Art.501-4(b) Class 1 Division 2, |
| 5) Cable trays in hazardous locations per NEC Art.502-4(b) Class 2 Division 2, and |
| 6) CL2 and CL3 applications. |
| Standards |
| UL Subject 13. |
| Passes UL and IEEE383 70,000BTU Flame Test. |
| NEC Article 725 Class 2 and Class 3 Circuits. |
|