INSTRUMENT CABLE - TINNED COPPER
INDIVIDUALLY SHIELDED PAIRS
TYPE PLTC, 105°C, 300VOLTS

Construction:
CONDUCTOR: STRANDED TINNED COPPER
INSULATION: FLAME RETARDANT PVC.
COLOR CODE: PAIRS ARE CODED BLACK AND RED.
ONE CONDUCTOR IN EACH PAIR IS ALSO NUMBERED FOR EASE OF IDENTIFICATION.
ASSEMBLY: INSULATED CONDUCTORS ARE TWISTED INTO PAIRS; TWISTED PAIRS INDIVIDUALLY SHIELDED WITH ALUMINUM/MYLAR TAPE SHIELD AND STRANDED TINNED COPPER DRAIN WIRE TO PROVIDE 100% SHIELDING COVERAGE.
SHIELDED PAIRS CABLED TOGETHER.
JACKET: SUNLIGHT AND MOISTURE RESISTANT, FLAME RETARDANT GRAY PVC.
 Charlotte Wire Part# ↓   Size AWG   Number of Pairs   Number of Conductor Strands   Insulation Thickness (in.)   Jacket Thickness (in.)   Overall Diameter (in.)   Approx. Net Wt. (Lbs/Mft)   Add to Quote Cart 
CW05101 22 2 7 0.015 0.042 .32" 42 Request Quote For This Product 
CW05102 22 3 7 0.015 0.042 .34" 54 Request Quote For This Product 
CW05103 22 4 7 0.015 0.042 .37" 66 Request Quote For This Product 
CW05104 22 6 7 0.015 0.053 .46" 101 Request Quote For This Product 
CW05105 22 9 7 0.015 0.053 .52" 143 Request Quote For This Product 
CW05106 22 11 7 0.015 0.053 .56" 165 Request Quote For This Product 
CW05107 22 19 7 0.015 0.063 .69" 270 Request Quote For This Product 
CW05108 22 51 7 0.015 0.075 1.05" 520 Request Quote For This Product 
CW05109 18 2 16 0.015 0.042 .38" 71 Request Quote For This Product 
CW05110 18 3 16 0.015 0.053 .43" 102 Request Quote For This Product 
CW05111 18 4 16 0.015 0.053 .49" 126 Request Quote For This Product 
CW05112 18 6 16 0.015 0.053 .56" 181 Request Quote For This Product 
CW05113 18 9 16 0.015 0.063 .65" 239 Request Quote For This Product 
CW05114 18 11 16 0.015 0.063 .73" 312 Request Quote For This Product 
CW05115 18 15 16 0.015 0.063 .81" 409 Request Quote For This Product 
Displaying 1 to 15 (of 15 products) Result Pages:  1 
Application
Instrumentation and Control Circuits rated 300volts or less.
Per NEC Article 725, approved for installation in
1) Cable trays indoors and outdoors,
2) raceways,
3) supported by a messenger wire,
4) hazardous locations per NEC Art.501-4(b) Class 1 Division 2,
5) Cable trays in hazardous locations per NEC Art.502-4(b) Class 2 Division 2, and
6) CL2 and CL3 applications.
Standards
UL Subject 13.
Passes UL and IEEE383 70,000BTU Flame Test.
NEC Article 725 Class 2 and Class 3 Circuits.