INSTRUMENT CABLE - OVERALL SHIELDED
NONSHIELDED PAIRS OR TRIADS - #18AWG
TYPE PLTC, 105°C, 300VOLTS
| Construction: |
| CONDUCTOR: |
7 STRANDED BARE COPPER. |
| INSULATION: |
FLAME RETARDANT PVC. |
| COLOR CODE: |
PAIRS ARE CODED BLACK AND WHITE; TRIADS ARE CODED BLACK, WHITE, AND RED. |
| ONE CONDUCTOR IN EACH PAIR OR TRIAD IS ALSO NUMBERED FOR EASE OF IDENTIFICATION. |
| ASSEMBLY: |
INSULATED CONDUCTORS ARE TWISTED INTO PAIRS OR TRIADS WITH AN APPROXIMATE 2" STAGGERED LAY OF TWIST TO REDUCE CROSSTALK. |
| TWISTED PAIRS CABLED WITH OVERALL ALUMINUM/MYLAR TAPE SHIELD AND STRANDED TINNED COPPER DRAIN WIRE TO PROVIDE 100% SHIELDING COVERAGE. |
| RIP CORD |
NYLON RIPCORD APPLIED UNDER JACKET TO HELP STRIP JACKET. |
| JACKET: |
SUNLIGHT AND MOISTURE RESISTANT, FLAME RETARDANT BLACK PVC. |
| Charlotte Wire Part# ↓ |
Size AWG |
Number of Pairs |
Number of Triads |
Insulation Thickness (in.) |
Jacket Thickness (in.) |
Overall Diameter (in.) |
Approx. Net Wt. (Lbs/Mft) |
Add to Quote Cart |
| CW05151 |
18 |
2 |
- |
0.015 |
0.04 |
.37" |
60 |
|
| CW05152 |
18 |
3 |
- |
0.015 |
0.05 |
.42" |
90 |
|
| CW05153 |
18 |
4 |
- |
0.015 |
0.05 |
.45" |
106 |
|
| CW05154 |
18 |
8 |
- |
0.015 |
0.05 |
.54" |
176 |
|
| CW05155 |
18 |
12 |
- |
0.015 |
0.06 |
.67" |
258 |
|
| CW05156 |
18 |
16 |
- |
0.015 |
0.06 |
.75" |
340 |
|
| CW05157 |
18 |
24 |
- |
0.015 |
0.07 |
.92" |
480 |
|
| CW05158 |
18 |
36 |
- |
0.015 |
0.07 |
1.07" |
675 |
|
| CW05159 |
18 |
50 |
- |
0.015 |
0.08 |
1.26" |
1040 |
|
| CW05160 |
18 |
- |
2 |
0.015 |
0.05 |
.42" |
90 |
|
| CW05161 |
18 |
- |
4 |
0.015 |
0.05 |
.46" |
155 |
|
| CW05162 |
18 |
- |
8 |
0.015 |
0.06 |
.64" |
322 |
|
| CW05163 |
18 |
- |
16 |
0.015 |
0.07 |
.89" |
480 |
|
| CW05164 |
18 |
- |
24 |
0.015 |
0.07 |
1.04" |
690 |
|
| Displaying 1 to 14 (of 14 products) |
Result Pages: 1 |
| Application |
| Instrumentation and Control Circuits rated 300volts or less. |
| Per NEC Article 725, approved for installation in |
| 1) Cable trays indoors and outdoors, |
| 2) raceways, |
| 3) supported by a messenger wire, |
| 4) hazardous locations per NEC Art.501-4(b) Class 1 Division 2, |
| 5) Cable trays in hazardous locations per NEC Art.502-4(b) Class 2 Division 2, and |
| 6) CL2 and CL3 applications. |
| Standards |
| UL Subject 13. |
| Passes UL and IEEE383 70,000BTU Flame Test. |
| NEC Article 725 Class 2 and Class 3 Circuits. |
|
|