INSTRUMENT CABLE - #18AWG
SHIELDED PAIRS OR TRIADS WITH OVERALL SHIELD
TYPE PLTC, 105°C, 300VOLTS

Construction:
CONDUCTOR: 7 STRANDED BARE COPPER.
INSULATION: FLAME RETARDANT PVC.
COLOR CODE: PAIRS ARE CODED BLACK AND WHITE; TRIADS ARE CODED BLACK, WHITE, AND RED.
ONE CONDUCTOR IN EACH PAIR OR TRIAD IS ALSO NUMBERED FOR EASE OF IDENTIFICATION.
PAIRS/TRIADS: INSULATED CONDUCTORS TWISTED INTO PAIRS OR TRIADS WITH AN APPROXIMATE 2" LAY OF TWIST TO REDUCE CROSSTALK.
TWISTED PAIRS OR TRIADS INDIVIDUALLY SHIELDED WITH ALUMINUM/MYLAR TAPE SHIELD AND STRANDED TINNED COPPER DRAIN WIRE.
OVERALL SHIELD: SHIELDED PAIRS CABLED TOGETHER WITH OVERALL ALUMINUM MYLAR TAPE SHIELD AND STRANDED TINNED COPPER DRAIN WIRE TO PROVIDE 100% SHIELDING COVERAGE.
RIP CORD NYLON RIPCORD APPLIED UNDER JACKET TO HELP STRIP JACKET.
JACKET: SUNLIGHT AND MOISTURE RESISTANT, FLAME RETARDANT BLACK PVC.
 Charlotte Wire Part# ↑   Size AWG   Number of Pairs   Number of Triads   Insulation Thickness (in.)   Jacket Thickness (in.)   Overall Diameter (in.)   Approx. Net Wt. (Lbs/Mft)   Add to Quote Cart 
CW05190 18 - 24 0.015 0.07 1.19" 825 Request Quote For This Product 
CW05189 18 - 16 0.015 0.07 .97" 568 Request Quote For This Product 
CW05188 18 - 12 0.015 0.06 .85" 418 Request Quote For This Product 
CW05187 18 - 8 0.015 0.06 .64" 365 Request Quote For This Product 
CW05186 18 - 4 0.015 0.05 .51" 178 Request Quote For This Product 
CW05185 18 - 2 0.015 0.05 .44" 109 Request Quote For This Product 
CW05184 18 50 - 0.015 0.08 1.40" 1180 Request Quote For This Product 
CW05183 18 36 - 0.015 0.07 1.18" 870 Request Quote For This Product 
CW05182 18 24 - 0.015 0.07 1.03" 614 Request Quote For This Product 
CW05181 18 16 - 0.015 0.06 .83" 440 Request Quote For This Product 
CW05180 18 12 - 0.015 0.06 .74" 327 Request Quote For This Product 
CW05179 18 8 - 0.015 0.05 .59" 220 Request Quote For This Product 
CW05178 18 4 - 0.015 0.05 .46" 138 Request Quote For This Product 
CW05177 18 2 - 0.015 0.05 .40" 85 Request Quote For This Product 
Displaying 1 to 14 (of 14 products) Result Pages:  1 
Application
Instrumentation and Control Circuits rated 300volts or less.
Per NEC Article 725, approved for installation in
1) Cable trays indoors and outdoors,
2) raceways,
3) supported by a messenger wire,
4) hazardous locations per NEC Art.501-4(b) Class 1 Division 2,
5) Cable trays in hazardous locations per NEC Art.502-4(b) Class 2 Division 2, and
6) CL2 and CL3 applications.
Standards
UL Subject 13.
Passes UL and IEEE383 70,000BTU Flame Test.
NEC Article 725 Class 2 and Class 3 Circuits.