INSTRUMENT CABLE - #16AWG
SHIELDED PAIRS OR TRIADS WITH OVERALL SHIELD
TYPE PLTC, 105°C, 300VOLTS
Click  for Printer Friendly Spec Sheet. | Construction: |
| CONDUCTOR: |
7 STRANDED BARE COPPER. |
| INSULATION: |
FLAME RETARDANT PVC. |
| COLOR CODE: |
PAIRS ARE CODED BLACK AND WHITE; TRIADS ARE CODED BLACK, WHITE, AND RED. |
| ONE CONDUCTOR IN EACH PAIR OR TRIAD IS ALSO NUMBERED FOR EASE OF IDENTIFICATION. |
| PAIRS/TRIADS: |
INSULATED CONDUCTORS TWISTED INTO PAIRS OR TRIADS WITH AN APPROXIMATE 2" LAY OF TWIST TO REDUCE CROSSTALK. |
| TWISTED PAIRS OR TRIADS INDIVIDUALLY SHIELDED WITH ALUMINUM/MYLAR TAPE SHIELD AND STRANDED TINNED COPPER DRAIN WIRE. |
| OVERALL SHIELD: |
SHIELDED PAIRS CABLED TOGETHER WITH OVERALL ALUMINUM MYLAR TAPE SHIELD AND STRANDED TINNED COPPER DRAIN WIRE TO PROVIDE 100% SHIELDING COVERAGE. |
| RIP CORD |
NYLON RIPCORD APPLIED UNDER JACKET TO HELP STRIP JACKET. |
| JACKET: |
SUNLIGHT AND MOISTURE RESISTANT, FLAME RETARDANT BLACK PVC. |
| Charlotte Wire Part# ↓ |
Size AWG |
Number of Pairs |
Number of Traids |
Insulation Thickness (in.) |
Jacket Thickness (in.) |
Overall Diameter (in.) |
Approx. Net Wt. (Lbs/Mft) |
Add to Quote Cart |
| CW05216 |
16 |
2 |
- |
0.015 |
0.05 |
.45" |
115 |
|
| CW05217 |
16 |
4 |
- |
0.015 |
0.05 |
.52" |
173 |
|
| CW05218 |
16 |
8 |
- |
0.015 |
0.06 |
.69" |
315 |
|
| CW05219 |
16 |
12 |
- |
0.015 |
0.06 |
.83" |
448 |
|
| CW05220 |
16 |
16 |
- |
0.015 |
0.07 |
.94" |
640 |
|
| CW05221 |
16 |
24 |
- |
0.015 |
0.07 |
1.16" |
842 |
|
| CW05222 |
16 |
36 |
- |
0.015 |
0.08 |
1.34" |
1230 |
|
| CW05223 |
16 |
50 |
- |
0.015 |
0.08 |
1.60" |
1630 |
|
| CW05224 |
16 |
- |
2 |
0.015 |
0.05 |
.49" |
140 |
|
| CW05225 |
16 |
- |
4 |
0.015 |
0.05 |
.60" |
230 |
|
| CW05226 |
16 |
- |
8 |
0.015 |
0.06 |
.78" |
400 |
|
| CW05227 |
16 |
- |
12 |
0.015 |
0.07 |
.98" |
605 |
|
| CW05228 |
16 |
- |
16 |
0.015 |
0.07 |
1.10" |
850 |
|
| CW05229 |
16 |
- |
24 |
0.015 |
0.08 |
1.35" |
1190 |
|
| Displaying 1 to 14 (of 14 products) |
Result Pages: 1 |
| Application |
| Instrumentation and Control Circuits rated 300volts or less. |
| Per NEC Article 725, approved for installation in |
| 1) Cable trays indoors and outdoors, |
| 2) raceways, |
| 3) supported by a messenger wire, |
| 4) hazardous locations per NEC Art.501-4(b) Class 1 Division 2, |
| 5) Cable trays in hazardous locations per NEC Art.502-4(b) Class 2 Division 2, and |
| 6) CL2 and CL3 applications. |
| Standards |
| UL Subject 13. |
| Passes UL and IEEE383 70,000BTU Flame Test. |
| NEC Article 725 Class 2 and Class 3 Circuits. |
|