INSTRUMENT CABLE - #16AWG
SHIELDED PAIRS OR TRIADS WITH OVERALL SHIELD
TYPE PLTC, 105°C, 300VOLTS

Construction:
CONDUCTOR: 7 STRANDED BARE COPPER.
INSULATION: FLAME RETARDANT PVC.
COLOR CODE: PAIRS ARE CODED BLACK AND WHITE; TRIADS ARE CODED BLACK, WHITE, AND RED.
ONE CONDUCTOR IN EACH PAIR OR TRIAD IS ALSO NUMBERED FOR EASE OF IDENTIFICATION.
PAIRS/TRIADS: INSULATED CONDUCTORS TWISTED INTO PAIRS OR TRIADS WITH AN APPROXIMATE 2" LAY OF TWIST TO REDUCE CROSSTALK.
TWISTED PAIRS OR TRIADS INDIVIDUALLY SHIELDED WITH ALUMINUM/MYLAR TAPE SHIELD AND STRANDED TINNED COPPER DRAIN WIRE.
OVERALL SHIELD: SHIELDED PAIRS CABLED TOGETHER WITH OVERALL ALUMINUM MYLAR TAPE SHIELD AND STRANDED TINNED COPPER DRAIN WIRE TO PROVIDE 100% SHIELDING COVERAGE.
RIP CORD NYLON RIPCORD APPLIED UNDER JACKET TO HELP STRIP JACKET.
JACKET: SUNLIGHT AND MOISTURE RESISTANT, FLAME RETARDANT BLACK PVC.
 Charlotte Wire Part# ↑   Size AWG   Number of Pairs   Number of Traids   Insulation Thickness (in.)   Jacket Thickness (in.)   Overall Diameter (in.)   Approx. Net Wt. (Lbs/Mft)   Add to Quote Cart 
CW05229 16 - 24 0.015 0.08 1.35" 1190 Request Quote For This Product 
CW05228 16 - 16 0.015 0.07 1.10" 850 Request Quote For This Product 
CW05227 16 - 12 0.015 0.07 .98" 605 Request Quote For This Product 
CW05226 16 - 8 0.015 0.06 .78" 400 Request Quote For This Product 
CW05225 16 - 4 0.015 0.05 .60" 230 Request Quote For This Product 
CW05224 16 - 2 0.015 0.05 .49" 140 Request Quote For This Product 
CW05223 16 50 - 0.015 0.08 1.60" 1630 Request Quote For This Product 
CW05222 16 36 - 0.015 0.08 1.34" 1230 Request Quote For This Product 
CW05221 16 24 - 0.015 0.07 1.16" 842 Request Quote For This Product 
CW05220 16 16 - 0.015 0.07 .94" 640 Request Quote For This Product 
CW05219 16 12 - 0.015 0.06 .83" 448 Request Quote For This Product 
CW05218 16 8 - 0.015 0.06 .69" 315 Request Quote For This Product 
CW05217 16 4 - 0.015 0.05 .52" 173 Request Quote For This Product 
CW05216 16 2 - 0.015 0.05 .45" 115 Request Quote For This Product 
Displaying 1 to 14 (of 14 products) Result Pages:  1 
Application
Instrumentation and Control Circuits rated 300volts or less.
Per NEC Article 725, approved for installation in
1) Cable trays indoors and outdoors,
2) raceways,
3) supported by a messenger wire,
4) hazardous locations per NEC Art.501-4(b) Class 1 Division 2,
5) Cable trays in hazardous locations per NEC Art.502-4(b) Class 2 Division 2, and
6) CL2 and CL3 applications.
Standards
UL Subject 13.
Passes UL and IEEE383 70,000BTU Flame Test.
NEC Article 725 Class 2 and Class 3 Circuits.