INSTRUMENT CABLE - OVERALL SHIELDED
NONSHIELDED PAIRS - #18AWG AND #16AWG
TYPE TC, 90°C, 600VOLTS
Click  for Printer Friendly Spec Sheet. | Construction: |
| CONDUCTOR: |
7 STRANDED BARE COPPER. |
| INSULATION: |
POLYVINYLCHLORIDE WITH 4 MILS NYLON JACKET TYPE TFN PER UL 62 (GASOLINE AND OIL RESISTANT). |
| COLOR CODE: |
PAIRS ARE COLOR CODED BLACK AND WHITE. |
| ONE CONDUCTOR IN EACH PAIR IS ALSO NUMBERED FOR EASE OF IDENTIFICATION. |
| ASSEMBLY: |
INSULATED CONDUCTORS ARE TWISTED INTO PAIRS WITH AN APPROXIMATE 2" STAGGERED LAY OF TWIST TO REDUCE CROSSTALK. |
| TWISTED PAIRS CABLED WITH OVERALL ALUMINUM/MYLAR TAPE SHIELD AND STRANDED TINNED COPPER DRAIN WIRE TO PROVIDE 100% SHIELDING COVERAGE. |
| RIP CORD |
NYLON RIPCORD APPLIED UNDER JACKET TO HELP STRIP JACKET. |
| JACKET: |
SUNLIGHT AND MOISTURE RESISTANT, FLAME RETARDANT BLACK PVC. |
| Charlotte Wire Part# ↓ |
Size AWG |
Number of Pairs |
Insulation Thickness (in.) |
Nylon Thickness (in.) |
Jacket Thickness (in.) |
Overall Diameter (in.) |
Approx. Net Wt. (Lbs/Mft) |
Add to Quote Cart |
| CW05251 |
18 |
2 |
0.015 |
0.004 |
0.045 |
.40" |
72 |
|
| CW05252 |
18 |
4 |
0.015 |
0.004 |
0.045 |
.48" |
112 |
|
| CW05253 |
18 |
8 |
0.015 |
0.004 |
0.06 |
.62" |
200 |
|
| CW05254 |
18 |
12 |
0.015 |
0.004 |
0.06 |
.73" |
285 |
|
| CW05255 |
18 |
16 |
0.015 |
0.004 |
0.06 |
.82" |
360 |
|
| CW05256 |
18 |
24 |
0.015 |
0.004 |
0.08 |
1.02" |
540 |
|
| CW05257 |
18 |
36 |
0.015 |
0.004 |
0.08 |
1.20" |
760 |
|
| CW05258 |
18 |
50 |
0.015 |
0.004 |
0.08 |
1.41" |
990 |
|
| CW05259 |
16 |
2 |
0.015 |
0.004 |
0.045 |
.45" |
98 |
|
| CW05260 |
16 |
3 |
0.015 |
0.004 |
0.045 |
.49" |
129 |
|
| CW05261 |
16 |
4 |
0.015 |
0.004 |
0.045 |
.54" |
160 |
|
| CW05262 |
16 |
8 |
0.015 |
0.004 |
0.06 |
.68" |
270 |
|
| CW05263 |
16 |
12 |
0.015 |
0.004 |
0.06 |
.81" |
378 |
|
| CW05264 |
16 |
16 |
0.015 |
0.004 |
0.08 |
.94" |
522 |
|
| CW05265 |
16 |
24 |
0.015 |
0.004 |
0.08 |
1.14" |
738 |
|
| CW05266 |
16 |
36 |
0.015 |
0.004 |
0.08 |
1.34" |
1048 |
|
| CW05267 |
16 |
50 |
0.015 |
0.004 |
0.08 |
1.58" |
1407 |
|
| CW05268 |
18 |
6 |
0.015 |
0.004 |
0.06 |
.57" |
168 |
|
| CW05270 |
16 |
6 |
0.015 |
0.004 |
0.06 |
.63" |
230 |
|
| Displaying 1 to 19 (of 19 products) |
Result Pages: 1 |
| Application |
| Control, Signal, or Lighting circuits rated 600Volts. |
| May be used as sunlight resistant, directly buried and wet or dry locations. |
| Per NEC Articles 336 and 392, approved for installation in |
| 1) raceways and cable tray systems including ladders, troughs, channels, solid bottom trays, and other similar structures, |
| 2) lighting, control, and signal circuits |
| 3) aerial locations where supported by a messenger wire |
| 4) hazardous locations per Art.501 Class 1 Division 2, |
| 5) Class 1 circuits as permitted in Article 725-21(B). |
| Standards |
| UL Standard 1277 for Type TC Cables. |
| Passes UL and IEEE383 70,000BTU Flame Test. |
| UL Standard 62 for TFN Conductors. |
| NEC Articles 336 and 392 for Tray Cable uses and constructions. |
|