INSTRUMENT CABLE - #18AWG
SHIELDED PAIRS OR TRIADS WITH OVERALL SHIELD
TYPE TC, 90°C, 600VOLTS
| Construction: |
| CONDUCTOR: |
7 STRANDED BARE COPPER. |
| INSULATION: |
POLYVINYLCHLORIDE WITH 4 MILS NYLON JACKET TYPE TFN PER |
| UL 62 (GASOLINE AND OIL RESISTANT). |
| COLOR CODE: |
PAIRS ARE CODED BLACK AND WHITE. |
| TRIADS ARE CODED BLACK. WHITE, AND RED. |
| ONE CONDUCTOR IN EACH PAIR OR TRIAD IS ALSO NUMBERED FOR EASE OF IDENTIFICATION. |
| PAIRS/TRIADS: |
INSULATED CONDUCTORS TWISTED INTO PAIRS OR TRIADS WITH AN APPROXIMATE 2" LAY OF TWIST. |
| TWISTED PAIRS OR TRIADS SHIELDED INDIVIDUALLY WITH ALUMINUM/MYLAR TAPE SHIELD AND STRANDED TINNED COPPER DRAIN WIRE. |
| OVERALL SHIELD: |
SHIELDED PAIRS CABLED TOGETHER WITH OVERALL ALUMINUM MYLAR TAPE SHIELD AND STRANDED TINNED COPPER DRAIN WIRE TO PROVIDE 100% SHIELDING COVERAGE. |
| RIP CORD |
NYLON RIPCORD APPLIED UNDER JACKET TO HELP STRIP JACKET. |
| JACKET: |
SUNLIGHT AND MOISTURE RESISTANT, FLAME RETARDANT BLACK PVC. |
| Charlotte Wire Part# ↓ |
Size AWG |
Number of Pairs |
Number of Triads |
Insulation Thickness (in.) |
Jacket Thickness (in.) |
Overall Diameter (in.) |
Approx. Net Wt. (Lbs/Mft) |
Add to Quote Cart |
| CW05271 |
18 |
2 |
- |
0.015 |
0.05 |
.43" |
90 |
|
| CW05272 |
18 |
4 |
- |
0.015 |
0.05 |
.50" |
139 |
|
| CW05273 |
18 |
8 |
- |
0.015 |
0.06 |
.67" |
252 |
|
| CW05274 |
18 |
12 |
- |
0.015 |
0.06 |
.81" |
350 |
|
| CW05275 |
18 |
16 |
- |
0.015 |
0.08 |
.94" |
476 |
|
| CW05276 |
18 |
20 |
- |
0.015 |
0.08 |
1.05" |
590 |
|
| CW05277 |
18 |
24 |
- |
0.015 |
0.08 |
1.16" |
678 |
|
| CW05278 |
18 |
36 |
- |
0.015 |
0.08 |
1.32" |
975 |
|
| CW05279 |
18 |
50 |
- |
0.015 |
0.08 |
1.56" |
1310 |
|
| CW05280 |
18 |
- |
2 |
0.015 |
0.045 |
.48" |
115 |
|
| CW05281 |
18 |
- |
4 |
0.015 |
0.06 |
.56" |
190 |
|
| CW05282 |
18 |
- |
8 |
0.015 |
0.06 |
.74" |
325 |
|
| CW05283 |
18 |
- |
12 |
0.015 |
0.08 |
.96" |
490 |
|
| CW05284 |
18 |
- |
16 |
0.015 |
0.08 |
1.04" |
622 |
|
| CW05285 |
18 |
- |
24 |
0.015 |
0.08 |
1.28" |
890 |
|
| CW05286 |
18 |
3 |
- |
0.015 |
0.05 |
.47" |
110 |
|
| CW05288 |
18 |
6 |
- |
0.015 |
0.06 |
.63" |
225 |
|
| Displaying 1 to 17 (of 17 products) |
Result Pages: 1 |
| Application |
| Control, Signal, or Lighting circuits rated 600Volts. |
| May be used as sunlight resistant, directly buried and wet or dry locations. |
| Per NEC Articles 336 and 392, approved for installation in |
| 1) raceways and cable tray systems including ladders, troughs, channels, solid bottom trays, and other similar structures, |
| 2) lighting, control, and signal circuits |
| 3) aerial locations where supported by a messenger wire |
| 4) hazardous locations per Art.501 Class 1 Division 2, |
| 5) Class 1 circuits as permitted in Article 725-21(B). |
| Standards |
| UL Standard 1277 for Type TC Cables. |
| Passes UL and IEEE383 70,000BTU Flame Test. |
| UL Standard 62 for TFN Conductors. |
| NEC Articles 336 and 392 for Tray Cable uses and constructions. |
|
|