XLP/CPE INSTRUMENT CABLE #16AWG
SINGLE SHIELDED PAIR OR TRIAD AND
MULTIPLE SHIELDED PAIRS/TRIADS W/ OVERALL SHIELD
TYPE TC, 90°C, 600VOLTS

Construction:
CONDUCTOR: 7 STRANDED TINNED COPPER.
INSULATION: THERMOSETTING FLAME-RETARDANT XLP.
CONDUCTOR IDENTIFICATION: SINGLE PAIR/TRIAD: PAIR IS CODED BLACK-WHITE AND TRIAD IS COLOR CODED BLACK-WHITE-RED(ICEA TABLE E-1).*
MULTIPAIRS/TRIADS: PAIRS ARE CODED BLACK-WHITE AND TRIADS ARE CODED BLACK-WHITE-RED(ICEA METHOD E-1).*
ONE CONDUCTOR IN EACH PAIR OR TRIAD IS ALSO NUMBERED.
PAIRS/TRIADS: INSULATED CONDUCTORS TWISTED INTO PAIRS OR TRIADS AND SHIELDED WITH ALUMINUM/MYLAR TAPE SHIELD AND STRANDED TINNED COPPER DRAIN WIRE.
OVERALL SHIELD: MULTIPLE SHIELDED PAIRS/TRIADS CABLED TOGETHER WITH OVERALL ALUM/MYLAR TAPE AND STRANDED TINNED DRAIN.
JACKET: SUNLIGHT RESISTANT, FLAME RETARDANT BLACK CPE.
 Charlotte Wire Part#* ↑   Size AWG   Number of Pairs   Number of Triads   Insulation Thickness (in.)   Jacket Thickness (in.)   Overall Diameter (in.)   Approx. Net Wt. (Lbs/Mft)   Add to Quote Cart 
CW05397 16 - 12 0.025 0.08 1.23" 740 Request Quote For This Product 
CW05396 16 - 8 0.025 0.08 1.02" 544 Request Quote For This Product 
CW05395 16 - 4 0.025 0.06 .77" 272 Request Quote For This Product 
CW05394 16 - 2 0.025 0.045 .62" 175 Request Quote For This Product 
CW05393 16 - 1 0.025 0.045 .37" 70 Request Quote For This Product 
CW05392 16 36 - 0.025 0.08 1.68" 1377 Request Quote For This Product 
CW05391 16 24 - 0.025 0.08 1.44" 948 Request Quote For This Product 
CW05390 16 20 - 0.025 0.08 1.29" 794 Request Quote For This Product 
CW05389 16 16 - 0.025 0.08 1.21" 673 Request Quote For This Product 
CW05388 16 12 - 0.025 0.08 1.06" 535 Request Quote For This Product 
CW05387 16 8 - 0.025 0.06 .87" 365 Request Quote For This Product 
CW05386 16 7 - 0.025 0.06 .82" 320 Request Quote For This Product 
CW05385 16 6 - 0.025 0.06 .78" 274 Request Quote For This Product 
CW05384 16 4 - 0.025 0.06 .68" 200 Request Quote For This Product 
CW05383 16 3 - 0.025 0.06 .61" 160 Request Quote For This Product 
CW05382 16 2 - 0.025 0.045 .56" 109 Request Quote For This Product 
CW05381 16 1 - 0.025 0.045 .35" 55 Request Quote For This Product 
Displaying 1 to 17 (of 17 products) Result Pages:  1 
* To specify ICEA Method 1 Table E-2(formerly K-2), add suffix "K2" to Charlotte Wire Number (Black-Red-Blue).
Application
Suitable for control or instrumentation circuits rated 600Volts in power plants and heavy industrial locations where flame-resistance, stability in heat, physical durability, and excellent reliability is needed.
May be used as sunlight resistant, directly buried, and wet or dry locations.
Per NEC Articles 336 and 392, approved for installation in
1) raceways and cable tray systems including ladders, troughs, channels, solid bottom trays, and other similar structures,
2) lighting, control, and signal circuits,
3) aerial locations where supported by a messenger wire,
4) hazardous locations per NEC Article 501 Class 1 Division 2, and
5) Class 1 circuits as permitted in NEC Article 725-21(B).
Standards
UL 1277 for Type TC Cables.
Passes UL and IEEE383 70,000 BTU and ICEA 210,000BTU flame test.
ICEA S-95-658/NEMA WC70 for Nonshielded 0 - 2KV Cables. (Formerly ICEA S-66-524/NEMA WC7).
NEC Articles 336 and 392 for Tray Cable Uses and Constructions.