XLP/CPE INSTRUMENT CABLE #16AWG
SINGLE SHIELDED PAIR OR TRIAD AND
MULTIPLE SHIELDED PAIRS/TRIADS W/ OVERALL SHIELD
TYPE TC, 90°C, 600VOLTS
| Construction: |
| CONDUCTOR: |
7 STRANDED TINNED COPPER. |
| INSULATION: |
THERMOSETTING FLAME-RETARDANT XLP. |
| CONDUCTOR IDENTIFICATION: |
SINGLE PAIR/TRIAD: PAIR IS CODED BLACK-WHITE AND TRIAD IS COLOR CODED BLACK-WHITE-RED(ICEA TABLE E-1).* |
| MULTIPAIRS/TRIADS: PAIRS ARE CODED BLACK-WHITE AND TRIADS ARE CODED BLACK-WHITE-RED(ICEA METHOD E-1).* |
| ONE CONDUCTOR IN EACH PAIR OR TRIAD IS ALSO NUMBERED. |
| PAIRS/TRIADS: |
INSULATED CONDUCTORS TWISTED INTO PAIRS OR TRIADS AND SHIELDED WITH ALUMINUM/MYLAR TAPE SHIELD AND STRANDED TINNED COPPER DRAIN WIRE. |
| OVERALL SHIELD: |
MULTIPLE SHIELDED PAIRS/TRIADS CABLED TOGETHER WITH OVERALL ALUM/MYLAR TAPE AND STRANDED TINNED DRAIN. |
| JACKET: |
SUNLIGHT RESISTANT, FLAME RETARDANT BLACK CPE. |
| Charlotte Wire Part#* ↑ |
Size AWG |
Number of Pairs |
Number of Triads |
Insulation Thickness (in.) |
Jacket Thickness (in.) |
Overall Diameter (in.) |
Approx. Net Wt. (Lbs/Mft) |
Add to Quote Cart |
| CW05397 |
16 |
- |
12 |
0.025 |
0.08 |
1.23" |
740 |
|
| CW05396 |
16 |
- |
8 |
0.025 |
0.08 |
1.02" |
544 |
|
| CW05395 |
16 |
- |
4 |
0.025 |
0.06 |
.77" |
272 |
|
| CW05394 |
16 |
- |
2 |
0.025 |
0.045 |
.62" |
175 |
|
| CW05393 |
16 |
- |
1 |
0.025 |
0.045 |
.37" |
70 |
|
| CW05392 |
16 |
36 |
- |
0.025 |
0.08 |
1.68" |
1377 |
|
| CW05391 |
16 |
24 |
- |
0.025 |
0.08 |
1.44" |
948 |
|
| CW05390 |
16 |
20 |
- |
0.025 |
0.08 |
1.29" |
794 |
|
| CW05389 |
16 |
16 |
- |
0.025 |
0.08 |
1.21" |
673 |
|
| CW05388 |
16 |
12 |
- |
0.025 |
0.08 |
1.06" |
535 |
|
| CW05387 |
16 |
8 |
- |
0.025 |
0.06 |
.87" |
365 |
|
| CW05386 |
16 |
7 |
- |
0.025 |
0.06 |
.82" |
320 |
|
| CW05385 |
16 |
6 |
- |
0.025 |
0.06 |
.78" |
274 |
|
| CW05384 |
16 |
4 |
- |
0.025 |
0.06 |
.68" |
200 |
|
| CW05383 |
16 |
3 |
- |
0.025 |
0.06 |
.61" |
160 |
|
| CW05382 |
16 |
2 |
- |
0.025 |
0.045 |
.56" |
109 |
|
| CW05381 |
16 |
1 |
- |
0.025 |
0.045 |
.35" |
55 |
|
| Displaying 1 to 17 (of 17 products) |
Result Pages: 1 |
| * To specify ICEA Method 1 Table E-2(formerly K-2), add suffix "K2" to Charlotte Wire Number (Black-Red-Blue). |
| Application |
| Suitable for control or instrumentation circuits rated 600Volts in power plants and heavy industrial locations where flame-resistance, stability in heat, physical durability, and excellent reliability is needed. |
| May be used as sunlight resistant, directly buried, and wet or dry locations. |
| Per NEC Articles 336 and 392, approved for installation in |
| 1) raceways and cable tray systems including ladders, troughs, channels, solid bottom trays, and other similar structures, |
| 2) lighting, control, and signal circuits, |
| 3) aerial locations where supported by a messenger wire, |
| 4) hazardous locations per NEC Article 501 Class 1 Division 2, and |
| 5) Class 1 circuits as permitted in NEC Article 725-21(B). |
| Standards |
| UL 1277 for Type TC Cables. |
| Passes UL and IEEE383 70,000 BTU and ICEA 210,000BTU flame test. |
| ICEA S-95-658/NEMA WC70 for Nonshielded 0 - 2KV Cables. (Formerly ICEA S-66-524/NEMA WC7). |
| NEC Articles 336 and 392 for Tray Cable Uses and Constructions. |
|
|