FREP/CPE INSTRUMENT CABLE #16AWG
SINGLE SHIELDED PAIR OR TRIAD AND
MULTIPLE SHIELDED PAIRS/TRIADS W/ OVERALL SHIELD
TYPE TC, 90°C, 600VOLTS
| Construction: |
| CONDUCTOR: |
7 STRANDED TINNED COPPER. |
| INSULATION: |
THERMOSETTING FLAME RETARDANT ETHYLENE PROPYLENE. |
| CONDUCTOR IDENTIFICATION: |
SINGLE PAIR/TRIAD: PAIR IS COLOR CODED BLACK-WHITE AND TRIAD IS COLOR CODED BLACK-WHITE-RED.* |
| MULTIPAIR/TRIADS: PAIRS ARE COLOR CODED BLACK-WHITE AND TRIADS ARE CODED BLACK-WHITE-RED.* |
| ONE CONDUCTOR IN EACH PAIR OR TRIAD IS ALSO NUMBERED. |
| PAIRS/TRIADS: |
INSULATED CONDUCTORS TWISTED INTO PAIRS OR TRIADS AND SHIELDED WITH ALUMINUM/MYLAR TAPE SHIELD AND STRANDED TINNED COPPER DRAIN WIRE. |
| OVERALL SHIELD: |
MULTIPLE SHIELDED PAIRS/TRIADS CABLED TOGETHER WITH OVERALL ALUM/MYLAR TAPE AND STRANDED TINNED DRAIN. |
| JACKET: |
SUNLIGHT RESISTANT, FLAME RETARDANT BLACK CPE. |
| Charlotte Wire Part#* ↑ |
Size AWG |
Number of Pairs |
Number of Triads |
Insulation Thickness (in.) |
Jacket Thickness (in.) |
Overall Diameter (in.) |
Approx. Net Wt. (Lbs/Mft) |
Add to Quote Cart |
| CW05436 |
16 |
- |
12 |
0.025 |
0.08 |
1.23" |
740 |
|
| CW05435 |
16 |
- |
8 |
0.025 |
0.08 |
1.02" |
544 |
|
| CW05434 |
16 |
- |
4 |
0.025 |
0.06 |
.77" |
272 |
|
| CW05433 |
16 |
- |
1 |
0.025 |
0.045 |
.37" |
70 |
|
| CW05432 |
16 |
36 |
- |
0.025 |
0.08 |
1.68" |
1377 |
|
| CW05431 |
16 |
24 |
- |
0.025 |
0.08 |
1.44" |
948 |
|
| CW05430 |
16 |
20 |
- |
0.025 |
0.08 |
1.29" |
794 |
|
| CW05429 |
16 |
16 |
- |
0.025 |
0.08 |
1.21" |
673 |
|
| CW05428 |
16 |
12 |
- |
0.025 |
0.08 |
1.06" |
535 |
|
| CW05427 |
16 |
8 |
- |
0.025 |
0.06 |
.87" |
365 |
|
| CW05426 |
16 |
7 |
- |
0.025 |
0.06 |
.82" |
320 |
|
| CW05425 |
16 |
6 |
- |
0.025 |
0.06 |
.78" |
274 |
|
| CW05424 |
16 |
4 |
- |
0.025 |
0.06 |
.68" |
200 |
|
| CW05423 |
16 |
3 |
- |
0.025 |
0.06 |
.61" |
160 |
|
| CW05422 |
16 |
2 |
- |
0.025 |
0.045 |
.56" |
109 |
|
| CW05421 |
16 |
1 |
- |
0.025 |
0.045 |
.35" |
55 |
|
| Displaying 1 to 16 (of 16 products) |
Result Pages: 1 |
| * To specify Black/Red pairs or Black/Red/Blue triads add suffix "K2" to Charlotte Wire Part Number. |
| Application |
| Suitable for control or instrumentation circuits rated 600Volts in power plants and heavy industrial locations where flame-resistance, stability in heat, physical durability, and excellent reliability is needed. |
| May be used as sunlight resistant, directly buried, and wet or dry locations. |
| Per NEC Articles 336 and 392, approved for installation in |
| 1) raceways and cable tray systems including ladders, troughs, channels, solid bottom trays, and other similar structures, |
| 2) lighting, control, and signal circuits, |
| 3) aerial locations where supported by a messenger wire, |
| 4) hazardous locations per NEC Article 501 Class 1 Division 2, and |
| 5) Class 1 circuits as permitted in NEC Article 725-21(B). |
| Standards |
| UL 1277 for Type TC Cables. |
| Passes UL & IEEE383 70,000BTU and |
| ICEA 210,000BTU flame test. |
| ICEA S-82-552 for 600V Instrumentation Cables. |
| NEC Articles 336 & 392 for Tray Cable uses and constructions. |
| Optional Constructions |
| XLP Insulation with CPE Jacket. |
|
|