XLP/HYPALON® INSTRUMENT CABLE - #18AWG
SINGLE SHIELDED PAIR OR TRIAD AND
MULTIPLE SHIELDED PAIRS/TRIADS W/ OVERALL SHIELD
TYPE TC, 90°C, 600VOLTS
| Construction: |
| CONDUCTOR: |
7 STRANDED TINNED COPPER. |
| INSULATION: |
FLAME RETARDANT CROSSLINKED POLYETHYLENE (XLP). |
| CONDUCTOR IDENTIFICATION: |
SINGLE PAIR/TRIAD: PAIR IS COLOR CODED BLACK-WHITE AND TRIAD IS COLOR CODED BLACK-WHITE-RED (ICEA TABLE E-1).* |
| MULTIPAIRS/TRIADS: PAIRS ARE COLOR CODED BLACK-WHITE AND TRIADS ARE CODED BLACK-WHITE-RED (ICEA METHOD E-1).* |
| ONE CONDUCTOR IN EACH PAIR OR TRIAD IS ALSO NUMBERED. |
| PAIRS/TRIADS: |
INSULATED CONDUCTORS TWISTED INTO PAIRS OR TRIADS AND SHIELDED WITH ALUMINUM/MYLAR TAPE SHIELD AND STRANDED TINNED COPPER DRAIN WIRE. |
| OVERALL SHIELD: |
MULTIPLE SHIELDED PAIRS/TRIADS CABLED TOGETHER WITH OVERALL ALUM/MYLAR TAPE AND STRANDED TINNED DRAIN. |
| JACKET: |
SUNLIGHT RESISTANT, FLAME RETARDANT BLACK HYPALON®. |
| Charlotte Wire Part#* ↑ |
Size AWG |
Number of Pairs |
Number of Triads |
Insulation Thickness (in.) |
Jacket Thickness (in.) |
Overall Diameter (in.) |
Approx. Net Wt. (Lbs/Mft) |
Add to Quote Cart |
| CW05462 |
18 |
- |
12 |
0.03 |
0.08 |
1.18" |
610 |
|
| CW05461 |
18 |
- |
8 |
0.03 |
0.08 |
.97" |
415 |
|
| CW05460 |
18 |
- |
4 |
0.03 |
0.06 |
.73" |
230 |
|
| CW05459 |
18 |
- |
1 |
0.03 |
0.045 |
.34" |
67 |
|
| CW05458 |
18 |
36 |
- |
0.03 |
0.08 |
1.64" |
1440 |
|
| CW05457 |
18 |
24 |
- |
0.03 |
0.08 |
1.39" |
950 |
|
| CW05456 |
18 |
16 |
- |
0.03 |
0.08 |
1.18" |
676 |
|
| CW05455 |
18 |
12 |
- |
0.03 |
0.08 |
1.06" |
540 |
|
| CW05454 |
18 |
8 |
- |
0.03 |
0.06 |
.84" |
348 |
|
| CW05453 |
18 |
4 |
- |
0.03 |
0.06 |
.65" |
204 |
|
| CW05452 |
18 |
2 |
- |
0.03 |
0.045 |
.53" |
115 |
|
| CW05451 |
18 |
1 |
- |
0.03 |
0.045 |
.32" |
56 |
|
| Displaying 1 to 12 (of 12 products) |
Result Pages: 1 |
| ® Hypalon® is a Dupont Trademark. (Also known as chlorosulfonated polyethylene or CSPE.) |
| * To specify ICEA Method 1 Table E-2 (formerly K-2), add suffix "K2" to Charlotte Wire Number (Black-Red-Blue). |
| Application |
| Suitable for control or instrumentation circuits rated 600Volts in power plants and heavy industrial locations where flame-resistance, stability in heat, physical durability, and excellent reliability is needed. |
| May be used as sunlight resistant, directly buried, and wet or dry locations. |
| Per NEC Articles 336 and 392, approved for installation in |
| 1) raceways and cable tray systems including ladders, troughs, channels, solid bottom trays, and other similar structures, |
| 2) lighting, control, and signal circuits, |
| 3) aerial locations where supported by a messenger wire, |
| 4) hazardous locations per NEC Article 501 Class 1 Division 2, and |
| 5) Class 1 circuits as permitted in NEC Article 725-21(B). |
| Standards |
| UL 1277 for Type TC Cables. |
| Passes UL and IEEE383 70,000 BTU and ICEA 210,000BTU flame test. |
| ICEA S-66-524 for Crosslinked Polyethylene Wire and Cable. |
| NEC Articles 336 & 392 for Tray Cable uses and constructions. |
| Optional Constructions |
| XLP Insulation with CPE Jacket. |
|
|