PORTABLE CONTROL CABLE
TYPE SOOW - #16AWG
90°C 600VOLTS UL, CSA, AND MSHA LISTED
| Construction: |
| CONDUCTOR: |
STRANDS OF #30AWG FLEXIBLE SOFT DRAWN BARE COPPER PER ASTM B-3. |
| INSULATION: |
EPDM RUBBER COLOR CODED PER ICEA METHOD TABLE E-1 OF ICEA S-73-532 (FORMERLY K-1) EXCEPT 3/C #16, WHICH IS BLACK, WHITE, AND GREEN. |
| ASSEMBLY: |
INSULATED CONDUCTORS ARE CABLED TOGETHER WITH FILLERS AS NEEDED AND A SUITABLE TAPE SEPARATOR. |
| JACKET: |
BLACK THERMOSET CPE RUBBER JACKET WHICH IS ABRASION, CHEMICAL, FLAME, OIL, OZONE, SUNLIGHT, AND WATER RESISTANT. |
| Charlotte Wire Part# ↑ |
Size AWG |
Number of Conductors |
Insulation Thickness (in.) |
Jacket Thickness (in.) |
Rating in Amps* |
Overall Diameter (in.) |
Approx. Net Wt. (Lbs/Mft) |
Add to Quote Cart |
| CW03110 |
16 |
60 |
0.03 |
0.125 |
3.5 |
1.38" |
1290 |
|
| CW03109 |
16 |
50 |
0.03 |
0.125 |
3.5 |
1.30" |
1160 |
|
| CW03108 |
16 |
40 |
0.03 |
0.11 |
4 |
1.11" |
860 |
|
| CW03107 |
16 |
37 |
0.03 |
0.11 |
4 |
1.09" |
820 |
|
| CW03106 |
16 |
36 |
0.03 |
0.11 |
4 |
1.09" |
805 |
|
| CW03105 |
16 |
30 |
0.03 |
0.11 |
4.5 |
1.00" |
732 |
|
| CW03104 |
16 |
24 |
0.03 |
0.095 |
4.5 |
.90" |
575 |
|
| CW03103 |
16 |
20 |
0.03 |
0.095 |
5 |
.83" |
489 |
|
| CW03102 |
16 |
16 |
0.03 |
0.095 |
5 |
.77" |
410 |
|
| CW03101 |
16 |
14 |
0.03 |
0.095 |
5 |
.72" |
360 |
|
| CW03100 |
16 |
12 |
0.03 |
0.08 |
5 |
.68" |
320 |
|
| CW03099 |
16 |
10 |
0.03 |
0.08 |
5 |
.65" |
260 |
|
| CW03098 |
16 |
9 |
0.03 |
0.08 |
7 |
.59" |
230 |
|
| CW03097 |
16 |
8 |
0.03 |
0.08 |
7 |
.56" |
210 |
|
| CW03096 |
16 |
7 |
0.03 |
0.08 |
7 |
.53" |
195 |
|
| CW03095 |
16 |
6 |
0.03 |
0.08 |
8 |
.53" |
185 |
|
| CW03094 |
16 |
5 |
0.03 |
0.08 |
8 |
.50" |
157 |
|
| CW03093 |
16 |
4 |
0.03 |
0.06 |
10 |
.42" |
120 |
|
| CW03092 |
16 |
3 |
0.03 |
0.06 |
13 |
.39" |
100 |
|
| CW03091 |
16 |
2 |
0.03 |
0.06 |
13 |
.37" |
82 |
|
| Displaying 1 to 20 (of 20 products) |
Result Pages: 1 |
| * Ampacities based on 30°C ambient temperature in air per the 2002 NEC, Table 400-5(A). |
| Values shown are for current carrying conductors. A grounding conductor, or one which carries only the |
| unbalance current from other conductors is not counted in determining current carrying capacity. |
| Application |
| For use in connection of portable equipment and appliances. |
| Also for use on signal and control circuits in industrial plants. |
| Designed for extra hard usage and for equipment that is exposed to chemicals, oils, sunlight, and moisture. |
| Suitable for wet location use, including submersion in water. |
| Standards |
| UL Standard 62 for flexible cords. |
| CSA Standard C22.2 No. 49 for flexible cords. |
| MSHA Approved: passes MSHA flame test. |
| UL & CSA Type SOW: Weather resistant/outdoor. |
|
|