PORTABLE CONTROL CABLE
TYPE SOOW - #14AWG
90°C 600VOLTS UL, CSA, AND MSHA LISTED
| Construction: |
| CONDUCTOR: |
41 STRANDS OF #30AWG FLEXIBLE SOFT DRAWN BARE COPPER PER ASTM B-3. |
| INSULATION: |
EPDM RUBBER COLOR CODED PER ICEA METHOD 1 TABLE E-1 PER ICEA S-73-532 (FORMERLY K-1) EXCEPT 3/C #14, WHICH IS BLACK, WHITE, AND GREEN. |
| ASSEMBLY: |
INSULATED CONDUCTORS ARE CABLED TOGETHER WITH FILLERS AS NEEDED AND A SUITABLE TAPE SEPARATOR. |
| JACKET: |
BLACK THERMOSET CPE RUBBER JACKET WHICH IS ABRASION, CHEMICAL, FLAME, OIL, OZONE, SUNLIGHT, AND WATER RESISTANT. |
| Charlotte Wire Part# ↓ |
Size AWG |
Number of Conductors |
Insulation Thickness (in.) |
Jacket Thickness (in.) |
Rating in Amps* |
Overall Diameter (in.) |
Approx. Net Wt. (Lbs/Mft) |
Add to Quote Cart |
| CW03121 |
14 |
2 |
.045" |
.080" |
18 |
0.50" |
145 |
|
| CW03122 |
14 |
3 |
.045" |
.080" |
18 |
0.53" |
172 |
|
| CW03123 |
14 |
4 |
.045" |
.080" |
15 |
0.57" |
211 |
|
| CW03124 |
14 |
5 |
.045" |
.095" |
12 |
0.65" |
260 |
|
| CW03125 |
14 |
6 |
.045" |
.095" |
12 |
0.70" |
316 |
|
| CW03126 |
14 |
7 |
.045" |
.095" |
10.5 |
0.70" |
350 |
|
| CW03127 |
14 |
8 |
.045" |
.095" |
10.5 |
0.74" |
375 |
|
| CW03128 |
14 |
10 |
.045" |
.095" |
7.5 |
0.85" |
470 |
|
| CW03129 |
14 |
12 |
.045" |
.095" |
7.5 |
0.88" |
530 |
|
| CW03130 |
14 |
14 |
.045" |
.095" |
7.5 |
0.95" |
595 |
|
| CW03131 |
14 |
16 |
.045" |
.110" |
7.5 |
1.00" |
690 |
|
| CW03132 |
14 |
20 |
.045" |
.110" |
7.5 |
1.09" |
815 |
|
| CW03133 |
14 |
24 |
.045" |
.110" |
6.8 |
1.22" |
970 |
|
| CW03134 |
14 |
30 |
.045" |
.125" |
6.8 |
1.38" |
1160 |
|
| CW03135 |
14 |
37 |
.045" |
.125" |
6 |
1.48" |
1390 |
|
| CW03136 |
14 |
40 |
.045" |
.125" |
6 |
1.54" |
1480 |
|
| CW03137 |
14 |
50 |
.045" |
.125" |
6 |
1.73" |
1880 |
|
| Displaying 1 to 17 (of 17 products) |
Result Pages: 1 |
| * Ampacities based on 30°C ambient temperature in air per the 2002 NEC, Table 400-5(A). |
| Values shown are for current carrying conductors. A grounding conductor, or one which carries only the unbalance current from other conductors is not counted in determining current carrying capacity. |
| Application |
| For use in connection of portable equipment and appliances. |
| Also for use on signal and control circuits in industrial plants. |
| Designed for extra hard usage and for equipment that is exposed to chemicals, oils, sunlight, and moisture. |
| Suitable for wet location use, including submersion in water. |
| Standards |
| UL Standard 62 for flexible cords. |
| CSA Standard C22.2 No. 49 for flexible cords. |
| MSHA Approved: passes MSHA flame test. |
| UL & CSA Type SOW: Weather resistant/outdoor. |
|
|