PORTABLE CONTROL CABLE
TYPE SOOW - #10AWG
90°C 600VOLTS UL, CSA, AND MSHA LISTED
Click  for Printer Friendly Spec Sheet. | Construction: |
| CONDUCTOR: |
104 STRANDS OF #30AWG FLEXIBLE SOFT DRAWN BARE COPPER PER ASTM B-3. |
| INSULATION: |
EPDM RUBBER COLOR CODED PER ICEA METHOD 1 TABLE E-1 OF ICEA S-73-532 (FORMERLY K-1), EXCEPT 3/C #10, WHICH IS BLACK, WHITE, AND GREEN. |
| ASSEMBLY: |
INSULATED CONDUCTORS ARE CABLED TOGETHER WITH FILLERS AS NEEDED AND A SUITABLE TAPE SEPARATOR. |
| JACKET: |
BLACK THERMOSET CPE RUBBER JACKET WHICH IS ABRASION, CHEMICAL, FLAME, OIL, OZONE, SUNLIGHT, AND WATER RESISTANT. |
| Charlotte Wire Part# ↓ |
Size AWG |
Number of Conductors |
Insulation Thickness (in.) |
Jacket Thickness (in.) |
Rating in Amps* |
Overall Diameter (in.) |
Approx. Net Wt. (Lbs/Mft) |
Add to Quote Cart |
| CW03170 |
10 |
2 |
.045" |
.095" |
30 |
0.63" |
240 |
|
| CW03171 |
10 |
3 |
.045" |
.095" |
30 |
0.66" |
300 |
|
| CW03172 |
10 |
4 |
.045" |
.095" |
25 |
0.71" |
360 |
|
| CW03173 |
10 |
5 |
.045" |
.095" |
20 |
0.77" |
461 |
|
| CW03174 |
10 |
6 |
.045" |
.095" |
20 |
0.83" |
515 |
|
| CW03175 |
10 |
7 |
.045" |
.095" |
17.5 |
0.83" |
550 |
|
| CW03176 |
10 |
8 |
.045" |
.095" |
17.5 |
0.91" |
645 |
|
| CW03177 |
10 |
10 |
.045" |
.110" |
12.5 |
1.06" |
810 |
|
| CW03178 |
10 |
12 |
.045" |
.110" |
12.5 |
1.12" |
908 |
|
| CW03179 |
10 |
16 |
.045" |
.110" |
12.5 |
1.24" |
1144 |
|
| CW03180 |
10 |
20 |
.045" |
.125" |
12.5 |
1.35" |
1410 |
|
| CW03181 |
10 |
24 |
.045" |
.125" |
12.5 |
1.46" |
1790 |
|
| CW03182 |
10 |
30 |
.045" |
.125" |
12.5 |
1.59" |
2140 |
|
| CW03183 |
10 |
40 |
.045" |
.125" |
12.5 |
1.90" |
2580 |
|
| Displaying 1 to 14 (of 14 products) |
Result Pages: 1 |
| * Ampacities based on 30°C ambient temperature in air per 2002 NEC, Table 400-5(A). |
| Values shown are for current carrying conductors. A grounding conductor, or one which carries only the unbalance current from other conductors is not counted in determining current carrying capacity. |
| Application |
| For use in connection of portable equipment and appliances. |
| Also for use on signal and control circuits in industrial plants. |
| Designed for extra hard usage and for equipment that is exposed to chemicals, oils, sunlight, and moisture. |
| Suitable for wet location use, including submersion in water. |
| Standards |
| UL Standard 62 for flexible cords. |
| CSA Standard C22.2 No. 49 for flexible cords. |
| MSHA Approved: passes MSHA flame test. |
| UL & CSA Type SOW: Weather resistant/outdoor. |
|