PORTABLE POWER CABLE
TYPE SOOW #8AWG THROUGH #2AWG
90°C, 600VOLTS, MSHA LISTED

Construction:
CONDUCTOR: FLEXIBLE STRANDED SOFT DRAWN BARE COPPER PER ASTM B-3.
INSULATION: EPDM RUBBER COLOR CODED PER ICEA METHOD 1 TABLE E-1 OF ICEA S-73-532 (FORMERLY K-1) EXCEPT 3 CONDUCTOR ITEMS WHICH ARE BLACK, WHITE, AND GREEN.
ASSEMBLY: INSULATED CONDUCTORS ARE CABLED TOGETHER WITH FILLERS AS NEEDED AND A SUITABLE TAPE SEPARATOR.
JACKET: BLACK THERMOSET CPE RUBBER JACKET WHICH IS ABRASION, CHEMICAL, FLAME, OIL, OZONE, SUNLIGHT, AND WATER RESISTANT.
 Charlotte Wire Part# ↑   Size AWG   Number of Conductors   Number of Strands   Jacket Thickness (in.)   Rating in Amps*   Overall Diameter (in.)   Approx. Net Wt. (Lbs/Mft)   Add to Quote Cart 
CW03205 2 5 133 0.08 64 1.42" 1650 Request Quote For This Product 
CW03204 2 4 133 0.08 80 1.19" 1310 Request Quote For This Product 
CW03203 2 3 133 0.08 95 1.10" 1060 Request Quote For This Product 
CW03202 2 2 133 0.08 95 1.05" 830 Request Quote For This Product 
CW03201 4 5 119 0.08 48 1.16" 1100 Request Quote For This Product 
CW03200 4 4 119 0.08 60 1.05" 880 Request Quote For This Product 
CW03199 4 3 119 0.08 70 .95" 720 Request Quote For This Product 
CW03198 4 2 119 0.08 70 .90" 595 Request Quote For This Product 
CW03197 6 5 103 0.08 36 .96" 780 Request Quote For This Product 
CW03196 6 4 103 0.08 45 .90" 645 Request Quote For This Product 
CW03195 6 3 103 0.06 55 .80" 512 Request Quote For This Product 
CW03194 6 2 103 0.06 55 .74" 390 Request Quote For This Product 
CW03193 8 5 65 0.06 28 .87" 558 Request Quote For This Product 
CW03192 8 4 65 0.06 35 .79" 470 Request Quote For This Product 
CW03191 8 3 65 0.06 40 .73" 370 Request Quote For This Product 
CW03190 8 2 65 0.06 40 .68" 300 Request Quote For This Product 
Displaying 1 to 16 (of 16 products) Result Pages:  1 
* Ampacities based on 30°C ambient temperature in air per the 2002 NEC, Table 400-5(A).
Values shown are for current carrying conductors. A grounding conductor, or one which carries only the unbalance current from other conductors is not counted in determining current carrying capacity.
Application
For use in connection of portable equipment and appliances.
Also for use on power circuits in industrial plants.
Designed for extra hard usage and for equipment that is exposed to chemicals, oils, sunlight, and moisture.
Suitable for wet location use, including submersion in water.
Standards
MSHA Approved: passes MSHA flame test.
Color Code
2/C Black, White
3/C Black, White, Green
4/C Black, White, Red, Green
5/C Black, White, Red, Green, Orange