THERMOCOUPLE EXTENSION WIRE
SINGLE PAIR 105°C PVC
SOLID, SHIELDED, UL TYPE PLTC, 300VOLTS

Construction:
CONDUCTOR: SOLID ALLOYS PER ANSI STANDARDS. (SEE TABLE BELOW.)
INSULATION: 15MILS POLYVINYL CHLORIDE(PVC) COLOR CODED PER ANSI STANDARDS.
ASSEMBLY: INSULATED CONDUCTORS ARE TWISTED WITH OVERALL ALUMINUM MYLAR TAPE SHIELD AND TINNED COPPER DRAIN WIRE FOR 100% SHIELDING COVERAGE.
JACKET: POLYVINYL CHLORIDE COLOR CODED PER ANSI STANDARDS.
RATED FOR CONTINUOUS USE FROM -20°C(-29°F) TO +105°C(221°F). THICKNESS PER UL PLTC STANDARD.
 Charlotte Wire Part# ↑   A.N.S.I Type   Size AWG   Insulation Thickness (in.)   Jacket Thickness (in.)   Overall Diameter (in.)   Approx. Net Wt. (Lbs/Mft)   Add to Quote Cart 
CW06207 KX 18 0.015 0.035 .23" 35 Request Quote For This Product 
CW06206 JX 18 0.015 0.035 .23" 35 Request Quote For This Product 
CW06205 RSX 16 0.015 0.035 .25" 39 Request Quote For This Product 
CW06204 RSX 20 0.015 0.035 .21" 27 Request Quote For This Product 
CW06203 TX 16 0.015 0.035 .25" 39 Request Quote For This Product 
CW06202 TX 20 0.015 0.035 .21" 27 Request Quote For This Product 
CW06201 EX 16 0.015 0.035 .25" 39 Request Quote For This Product 
CW06200 EX 20 0.015 0.035 .21" 27 Request Quote For This Product 
CW06199 KX 16 0.015 0.035 .25" 39 Request Quote For This Product 
CW06198 KX 20 0.015 0.035 .21" 27 Request Quote For This Product 
CW06197 JX 16 0.015 0.035 .25" 39 Request Quote For This Product 
CW06196 JX 20 0.015 0.035 .21" 27 Request Quote For This Product 
Displaying 1 to 12 (of 12 products) Result Pages:  1 
Application
Suitable for the relay of temperature measurement signals in petrochemical plants, power plants, and fiber plants.
Per NEC Art.725, approved for installation in
1) cable trays indoors and outdoors,
2) raceways,
3) supported by a messenger wire,
4) hazardous locations per NEC Article 501-4(b) Class 1 Division 2, and
5) cable trays in hazardous locations per NEC Article 502-4(b) Class 2 Division 2.
Standards
UL Subject 13.
Passes UL and IEEE 383 70,000BTU flame test.
NEC Article 725 Class 2 & 3.
Optional Constructions
Special calibration tolerance.
Other sizes including 18AWG.
Thermocouple Identification
A.N.S.I. Type Positive Wire Type Negative Wire Type Positive Wire Color Negative Wire Color Overall Jacket Color Limits of Error (°C)
JX Iron Constantan White Red Black +/-2.2Deg C
KX Chromel Alumel Yellow Red Yellow +/-2.2Deg C
EX Chromel Constantan Purple Red Purple +/-1.7Deg C
TX Copper Constantan Blue Red Blue +/-1.0Deg C
RSX* Copper Cu Alloy #11 Black Red Green +/-5.0Deg C
* Types RX and SX utilize the same ANSI conductor alloys and color code.