THERMOCOUPLE EXTENSION WIRE-EX & TX
SHIELDED PAIRS WITH OVERALL SHIELD
105°C PVC, UL PLTC, 300VOLTS
| Construction: |
| CONDUCTOR: |
SOLID ALLOYS PER ANSI STANDARDS. (SEE TABLE BELOW.)
|
| INSULATION: |
15MILS PVC COLOR CODED PER ANSI STANDARDS.
|
| PAIRS: |
INSULATED CONDUCTORS TWISTED INTO PAIRS.
|
| COLOR CODED PER ANSI STANDARDS.
|
| ONE CONDUCTOR IN EACH IS ALSO NUMBERED FOR PAIR IDENTIFICATION.
|
| PAIRS CABLED TOGETHER WITH ALUMINUM MYLAR TAPE SHIELD AND TINNED COPPER DRAIN TO PROVIDE 100% SHIELDING COVERAGE.
|
| OVERALL SHIELD: |
SHIELDED PAIRS CABLED TOGETHER WITH OVERALL ALUMINUM MYLAR TAPE SHIELD AND TINNED COPPER DRAIN WIRE.
|
| RIP CORD |
APPLIED UNDER JACKET TO HELP STRIP JACKET.
|
| JACKET: |
SUNLIGHT AND MOISTURE RESISTANT, FLAME RETARDANT PVC COLOR CODED PER ANSI STANDARDS.
|
| Charlotte Wire Part# ↓ |
A.N.S.I Type |
Size AWG |
Number of Pairs |
Jacket Thickness (in.) |
Overall Diameter (in.) |
Approx. Net Wt. (Lbs/Mft) |
Add to Quote Cart |
| CW06321 |
EX |
20 |
2 |
0.04 |
.35" |
60 |
|
| CW06322 |
EX |
20 |
4 |
0.05 |
.46" |
104 |
|
| CW06323 |
EX |
20 |
8 |
0.05 |
.57" |
170 |
|
| CW06324 |
EX |
20 |
12 |
0.06 |
.67" |
255 |
|
| CW06325 |
EX |
20 |
16 |
0.06 |
.75" |
305 |
|
| CW06326 |
EX |
20 |
24 |
0.06 |
.92" |
460 |
|
| CW06327 |
EX |
20 |
36 |
0.07 |
1.05" |
630 |
|
| CW06328 |
TX |
20 |
2 |
0.04 |
.35" |
60 |
|
| CW06329 |
TX |
20 |
4 |
0.05 |
.46" |
104 |
|
| CW06330 |
TX |
20 |
8 |
0.05 |
.57" |
170 |
|
| CW06331 |
TX |
20 |
12 |
0.06 |
.67" |
255 |
|
| CW06332 |
TX |
20 |
16 |
0.06 |
.75" |
305 |
|
| CW06333 |
TX |
20 |
24 |
0.06 |
.92" |
460 |
|
| CW06334 |
TX |
20 |
36 |
0.07 |
1.05" |
630 |
|
| Displaying 1 to 14 (of 14 products) |
Result Pages: 1 |
| Application |
| Suitable for the relay of temperature measurement signals in petrochemical plants, power plants, and fiber plants.
|
| Per NEC Art.725, approved for installation in
|
| 1) cable trays indoors and outdoors,
|
| 2) raceways,
|
| 3) supported by a messenger wire,
|
| 4) hazardous locations per NEC Article 501-4(b) Class 1 Division 2, and
|
| 5) cable trays in hazardous locations per NEC Article 502-4(b) Class 2 Division 2.
|
| Standards |
| UL Subject 13.
|
| Passes UL and IEEE 383 70,000BTU flame test.
|
| NEC Article 725 Class 2 & 3.
|
| Optional Constructions |
| Other sizes including 18 & 16.
|
| Type RX and SX alloy.
|
| Thermocouple Identification |
| A.N.S.I. Type |
Positive Wire Type |
Negative Wire Type |
Positive Wire Color |
Negative Wire Color |
Overall Jacket Color |
Limits of Error (°C)
|
| JX |
Iron |
Constantan |
White |
Red |
Black |
+/-2.2°C
|
| KX |
Chromel |
Alumel |
Yellow |
Red |
Yellow |
+/-2.2°C
|
| EX |
Chromel |
Constantan |
Purple |
Red |
Purple |
+/-1.7°C
|
| TX |
Copper |
Constantan |
Blue |
Red |
Blue |
+/-1.0°C
|
| RSX* |
Copper |
Cu Alloy #11 |
Black |
Red |
Green |
+/-5.0°C
|
| * Types RX and SX utilize the same ANSI conductor alloys and color code. |
|
|
|
|
|
|
|
|